Modbus Map SOLECTRIA XGI 1500 (Rev A)
DOCR-XXXXXX
5 of 30
Power Limiting
4
This feature allows the inverter to reduce the output from what it could produce given available resources.
Power limiting request typically occurs because of transmission congestion or lack of transmission access. It
can also occur due to excess generation during low load periods.
The image below shows the default setting of Power Limiting. The default state of this feature is deactivated.
Example:
If the cutomer wants to enable this feature and run the inverter at 80% of rated power. The procedure via the
web-based GUI is shown below.
Write “ 80.0 ” to Power Limit
Click the little box on the top left corner of the configuration window to enable Power Limiting