Modbus Map SOLECTRIA XGI 1500 (Rev A)
DOCR-XXXXXX
22 of 30
The alternative method is to use software which supports Modbus TCP/IP. The register address is shown
below.
To implement the same curve, the procedure is shown below.
Write “ 16 ” to register 40393 for HV2 Disconnect Time
Write “ 1200 ” to register 40394 for HV2 Volt Threshold
Write “ 100 ” to register 40397 for HV1 Disconnect Time
Write “ 1100 ” to register 40398 for HV1 Volt Threshold
Write “ 150 ” to register 40331 for LV3 Disconnect Time
Write “ 500 ” to register 40332 for LV3 Volt Threshold
Write “ 1100 ” to register 40335 for LV2 Disconnect Time
Write “ 700 ” to register 40336 for LV2 Volt Threshold
Write “ 2100 ” to register 40339 for LV1 Disconnect Time
Write “ 880 ” to register 40340 for LV1 Volt Threshold