2 Specifications and Settings
2.1.2 400 V Specifications
13
2.2 DIP Switch Settings
1
2
3
4
DIP Switches
Rotary
Switches
(used to
set IP
address)
Rotary Switch 1
Rotary Switch 0
Switch
Name
Setting
Operating Mode
Setting for
Normal
Operation
Details
1
STOP
ON
User program execution
inhibited
OFF
Inhibits user program execution
OFF
Normal operation
2
SUP
ON
Firmware programming
mode
OFF
Enables servo controller firmware
programming. This mode can also be
performed via web UI without changing
the DIP switch.
OFF
Normal operation
3
INIT
ON
Configuration bypass
mode
OFF
Set to ON to bypass the stored
configuration (e.g. in case of a
configuration problem that prevents
servo controller startup)
OFF
Normal operation
4
E-INIT
ON
Normal operation
OFF
Rotary switches used to set IP address
OFF
Rotary switches ignored
IP address is set from configuration
settings in servo controller