9 Web Interface
50
YASKAWA ELECTRIC
SIEP C730600 89C YASKAWA AC Drive Option SI-EP3 Technical Manual
Settings Page
The Settings page sets web page behavior parameters. Access is restricted unless a valid password is entered.
Figure 25
Figure 26 Settings Page View
Security Login
Click “Login” and enter a valid password. The button text will change to “Log out” and the status will change to “Logged
in”.
Note:
The default security password is “
yaskawa
”.
This password can be changed in the “Change Password” section of the Settings page. Entering a valid password allows
access to the settings in the Settings page, Email Alerts page, and the Parameter Access page.
Webpage Password
To change the password, enter the new password in the “New Password:” and “Confirm Password:” text boxes then click
“Save password”.
Webpage Settings
The values displayed in the various tabs are refreshed at the rate defined in the “Data Update Time” select box. The Data
Update Time can be set to 250 ms, 500 ms, 1 second, 2 seconds, or 5 seconds.
Email Settings
The “Email Server IP Address” text box must contain the IP address of the email server. The subnet address is configured
in drive parameters F7-05 through F7-08. The configured email alerts will use the server at this address when sending
emails.
Enter the email server port in the “Email Server Port” text box.
The value in the “From’ Email Address” text box identifies the origin of the email alerts to the recipient.
Click “Save Email Settings” to save the email settings to the option.