11 Input Assemblies (Converter Produces)
YASKAWA
SIEP C730600 0DB EtherNet/IP Technical Manual
83
Input Instance
Word
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
19
Error Code (High Byte)
10
20
Alarm Code 2 (Low Byte)
21
Alarm Code 2 (High Byte)
11
22
Alarm Code 3 (Low Byte)
23
Alarm Code 3 (High Byte)
12
24
Terminal A3 Input (Low Byte)
25
Terminal A3 Input (High Byte)
13
26
Digital Input (Low Byte)
27
Digital Input (High Byte)
14
28
Terminal A1 Input (Low Byte)
29
Terminal A1 Input (High Byte)
15
30
-
31
-
16 - 19
32 - 39
Reserved
Name
Description
Running
Running
0: Stop
1: Running
During Regenerative Operation
During Regenerative Operation
0: Converter not in regenerative operation
1: Converter in regenerative operation
Reset
Reset
0: -
1: Reset
During Run - Operation Ready
0: Not Ready
1: Ready
Ready
Ready
0: Not Ready
1: Ready
Alarm
Alarm
0: No Alarm
1: Alarm
Faulted
Faulted
0: No Fault
1: Fault
oPE
oPE
0: -
1: oPExx
Uv
Undervoltage
0: -
1: Undervoltage
LOCAL/REMOTE
Run command is from network
0: Run command is not from network
1: Run command is from network
Multi-Function Digital Output 1
Terminal M1/M2 (varies by converter model)
0: M1/M2 OFF
1: M1/M2 ON
This function is enabled only when H2-01 is set to F.
Note:
The names of the digital outputs are different for different converter series.
Multi-Function Digital Output 2
Terminal M3/M4 (varies by converter model)
0: M3/M4 OFF
1: M3/M4 ON
This function is enabled only when H2-02 is set to F.
Note:
The names of the digital outputs are different for different converter series.
Multi-Function Digital Output 3
Terminal M5/M6 (varies by converter model)