Option Connection Diagram
Figure 5.28 Option Connection Diagram
*1
Connect the specified ground wire for installations on 1000-series, GA500, HV600, and FP605 drives. The ground wire is not
necessary for installation on GA700 or GA800 drives.
■
Communication Cable Specifications
The option modular connector CN1 port 1 and port 2 act as a switch to allow for flexibility in cabling topology.
Users may employ a traditional star network topology using either CN1 port 1 or CN1 port 2 on the option.
Alternatively, a daisy-chained approach may be employed by using both CN1 port 1 and CN1 port 2. The daisy-
chained approach reduces the requirements of Ethernet switch ports. A ring topology is also possible. RSTP or
DLR are available to be used in a ring topology.
A - PLC
B - Switch
C - Drives
Figure 5.29 Communication Cable Specifications
◆
EDS Files
For easy network implementation of drives equipped with the option, an EDS file can be obtained from: U.S.:
http://www.yaskawa.com Europe: http://www.yaskawa.eu.com Japan: http://www.e-mechatronics.com Other
areas: Check the back cover of these manuals. For questions, contact Yaskawa or a Yaskawa representative.
Note:
Download the EDS file for SI-EN3D option. The SI-EN3D will not function as a slave in the network without the appropriate EDS file.