8.2 Setup Procedure
8-3
8
Set-up Procedure for Semi-closed Loop Control
8.2.1
Feedback Option Module Set-up
The scale parameters must be written into the module via the SERVOPACK using the S software
engineering tool.
Note: This feature is available in S Version 5.6.1 and later.
(1) Set-up Procedure
1.
Install a motor, scale and SERVOPACK.
2.
Request the motor parameter file of the installed motor from YASKAWA Europe GmbH.
3.
In S select “Parameters > Parameter edit”.
Set parameter Pn00B.3 = 1.
4.
Start “Setup > Motor parameter scale write” in S.
5.
Write the parameters of the motor parameter file to the scale.
Note: Refer to S Operation Manual for information on how to write parameters using S.
USB cable
Personal Computer
S
Scale parameter file
Write scale parameters into the feedback
option module via SGDV SERVOPACK
SGDV SERVOPACK
Linear Motor
USB cable
Personal Computer
S
Scale parameter file
Write scale parameters into the feedback
option module via SGDV SERVOPACK
SGDV SERVOPACK
Motor