4.3 CPU Unit Specifications
System Register Specifications
4-22
User Operation Error Status
The data in these registers give details when an operation error occurs in a user program.
Error Data
SW00060 and
SW00061
Reserved for system.
SW00062 to
SW00065
Name of task that caused the error
SW00066 and
SW00067
Reserved for system.
SW00068
Year When Error Occurred
SW00069
Month When Error Occurred
SW00070
Day of Week When Error Occurred
SW00071
Day When Error Occurred
SW00072
Hour When Error Occurred
SW00073
Minutes When Error Occurred
SW00074
Seconds When Error Occurred
SW00075
Milliseconds When Error Occurred
SW00076
xyzz hex
Slot Where the Module Synchronization Error
Was Detected (x: Rack number from 1 to 7, y:
unit number from 1 to 4, zz: slot number from
01 to 09)
SW00077 to
SW00079
Reserved for system.
Drawing Type Error Description Register Address
Contents
DWG.A
Error Count
SW00080
• Error Count
Gives the number of errors that have occurred.
• Error Code
Gives the details of the error.
0
hex: Operation error
x
hex (x = 1, 2, 3): Index error
Error Code
SW00081
DWG.I
Error Count
SW00082
Error Code
SW00083
DWG.H
Error Count
SW00084
Error Code
SW00085
Reserved for system.
SW00086,
SW00087
DWG.L
Error Count
SW00088
Error Code
SW00089
Continued from previous page.
Name
Register
Address
Contents