3.2 Function Modules
Data Logging
3-78
15.
Click the
OK
Button.
The Sampling and Trigger Dialog Box closed.
To automatically start logging when the power supply is turned ON, set the Start Trigger to
the following condition.
• When the saving destination is set to USB memory:
Setting example: Start trigger SB006540 = ON
Note: The SB006540 register turns ON when a USB memory device is detected.
• When the saving destination is set to built-in RAM disk:
Setting example: Start trigger SB000001 or SB000003 = ON
Note: The SB000001 register turns ON during the first scan of the high-speed scan.
The SB000003 register turns ON during the first scan of the low-speed scan.
In the following example, the output conditions are set to log only the data in the shaded
region.
Setting example: Condition A >= Upper limit, Condition B <= Lower limit, Compound con-
dition = OR
Click the
Cancel
Button to return to the Logging 1 Dialog Box without registering the set-
tings.
Example
Example
Upper limit
Lower limit
Logged data
Logged data
Information