PP.P5G5.03.Troubleshoot

Page 57

Rev. 06/11/2003

Soft Charge Contactor

Part Numbers:

Inverter Model Inverter Model

Mfg. Part

YEA Code

Contactor

Number

Number

Number

Number

Specifications Designation

(G5)

(PC5)

230V

230V

CIMR-

CIMR-

G5U20P4

P5U20P4

G5U20P7

P5U20P7

VSB-24MC

POR003011

G5U21P5

P5U21P5

G5U22P2

P5U22P2

HE1AN-DC24V

POR003013

G5U23P7

P5U23P7

DC 24V

MC1

G5U25P5

P5U25P5

HE2AN-DC24V

POR003014

G5U27P5

P5U27P5

G5U2011

P5U2011

G7J-4A-B-DC24V POR003012

G5U2015

P5U2015

460V

460V

G5U40P4

P5U40P4

G5U40P7

P5U40P7

JC2AF-B-DC24V POR003015

G5U41P5

P5U41P5

G5U42P2

P5U42P2

G5U43P7

P5U43P7

DC 24V

MC1

G5U44P0

P5U44P0

HE2AN-DC24V

POR003014

G5U45P5

P5U45P5

G5U47P5

P5U47P5

HP-20GU

MC003260

G5U4011

P5U4011

G7J-4A-B-DC24V POR003012

G5U4015

P5U4015

Содержание GPD 506/P5

Страница 1: ...PP P5G5 03 Troubleshoot Page 1 Rev 06 11 2003 Yaskawa Electric America Unit Troubleshooting Manual Section Three Fault Codes Appendix GPD 506 P5 and GPD 515 G5 0 4 160kW ...

Страница 2: ...06 11 2003 Section Three Fault Codes GPD 515 G5 DSPL ENTER DIGITAL OPERATOR JVOP 131U FREF FOUT IOUT ACCEL F R V F VMTR FLA PID DECEL FBIAS OC RUN STOP RESET LOCAL REMOTE REMOTE REF SEQ kWout MONTR FGAIN kWsav PRGM GPD 505 P5 GPD 506 P5 ...

Страница 3: ...red faults The fault codes can be grouped into 3 categories Major Fault Motor coasts to a stop the fault is displayed on the digital operator and the fault relay is activated Minor Fault Operation continues and the fault flashes on the digital operator The fault relay does not activate Parameter Setting Error Inverter can t run The fault is displayed on the digital operator and the fault relay is ...

Страница 4: ...power supply 460V Units 55kW 160kW monitors the 15V power supply UV2 CTL PS Undervolt Uu2 Possible Cause s Single phase condition on the input low input voltage at L1 L2 and L3 Corrective Action Check the three phase input voltage verify L2 05 for 515 G5 units Possible Cause s External load connected pulling down the inverter power supplies Corrective Action Repair or replace the power gate drive ...

Страница 5: ...ntacts on contactor are dirty contactor does not function mechanically Corrective Action Check the contactor check the ribbon cable from the control board to the gate drive board Possible Cause s High input voltage at L1 L2 and L3 The deceleration time is set too short Power factor correction capacitors are being used on the input to the inverter Corrective Action Check the input circuit verify th...

Страница 6: ...Remove the motor and run the inverter without the motor Check the motor for a phase to phase short Check the inverter for a phase to phase short at the output Possible Cause s Motor lead shorted to ground DCCT defective Corrective Action Remove the motor and run the inverter without the motor Check the motor for a phase to ground short Check the output current with a clamp on meter to verify the D...

Страница 7: ...erform the checks without with power starting on page 10 Replace the shorted component s then replace the defective fuse 505 Possible Cause s Shorted inverter output phase to phase shorted motor locked rotor Corrective Action Remove the motor and run the inverter without the motor Check the motor for a phase to phase short Check the inverter for a phase to phase short at the output Fault Codes Maj...

Страница 8: ...erter 120 or150 of inverter rated current for 1 minute 515 150 for 1 minute 505 and 506 120 or 150 depending on drive capacity and setting parameter n116 OL2 Inv Overloaded ol2 Possible Cause s Motor is overloaded Corrective Action Verify the program settings reduce the load on the motor Possible Cause s Motor is overloaded Corrective Action Verify the program settings reduce the load on the motor...

Страница 9: ...omer programmable current detection Response may be selected A minor fault contact output can be programmed by using the multi function outputs 505 Possible Cause s Motor is overloaded Corrective Action Verify the program settings reduce the load on the motor Possible Cause s Motor is overloaded Corrective Action Verify the program settings reduce the load on the motor Fault Codes Major Fault Moto...

Страница 10: ... incorrectly n083 for 506 P5 L8 05 for 515 G5 Corrective Action Tighten the terminal screws check the input voltage verify the program settings Possible Cause s Open phase on the output of the inverter Loose terminal screws at terminals T1 T2 or T3 Program parameters set incorrectly Corrective Action Tighten the terminal screws check the output voltage verify the program settings Fault Codes Major...

Страница 11: ...ot be set correctly Corrective Action Check the load on the motor verify the program settings F1 08 PG Overspeed Level and F1 09 PG Overspeed Time Possible Cause s The Pulse Generator feedback wires may be broken or not properly connected to the PG feedback option board Corrective Action Check for a broken wire or a loose connection from the Pulse Generator verify the program settings 505 Fault Co...

Страница 12: ... outputs RH DynBrk Resistor Possible Cause s Shorted braking transistor high DC bus voltage defective braking resistor Corrective Action Replace defective transistor or resistor monitor DC bus level Possible Cause s Overhauling load extended braking duty cycle defective braking resistor Corrective Action Verify braking duty cycle monitor DC bus voltage replace resistor 505 N A N A Fault Codes Majo...

Страница 13: ...s set too low load torque is excessively large Corrective Action Verify the program setting L7 03 forward regen torque limit and L7 04 reverse regen torque limit extend the deceleration time Possible Cause s Torque limit or zero servo gain set too low load torque excessively large PG signal noise Corrective Action Verify the program parameters B9 01 zero servo gain and torque limit settings L7 01 ...

Страница 14: ...r 505 Fault Codes Major Fault Motor coasts to a stop the fault is displayed on the digital operator and the fault relay is activated The inverter will stop if the digital operator is removed when the inverter is commanded to run through the digital operator OPR Oper Disconnect Possible Cause s The operator is not attached broken operator cable Corrective Action Attach the digital operator check th...

Страница 15: ...n is broken master has stopped communicating Corrective Action Check all connections verify all user side software configurations E 15 SI F G Com Err After initial communication has been established the connection was then lost Response may be selected 505 N A N A Fault Codes Major Fault Motor coasts to a stop the fault is displayed on the digital operator and the fault relay is activated E 10 and...

Страница 16: ...ll user side software configurations 505 N A Fault Codes Major Fault Motor coasts to a stop the fault is displayed on the digital operator and the fault relay is activated Possible Cause s Connection is broken master has stopped communicating Corrective Action Check all connections verify all user side software configurations CE Memobus Com Err Transmission error Control data was not received norm...

Страница 17: ... external fault condition exists connected to terminal number 3 Corrective Action Check for an external condition verify the program parameters Possible Cause s An external fault condition exists connected to one of the terminals 4 5 6 7 or 8 Corrective Action Check for an external condition verify the program parameters 505 Fault Codes Major Fault Motor coasts to a stop the fault is displayed on ...

Страница 18: ... condition at terminal S2 verify the program parameters ef0 External fault from serial communication Possible Cause s An external fault condition exists Corrective Action Check for an external condition verify the program parameters 505 EF0 External Fault Fault Codes Major Fault Motor coasts to a stop the fault is displayed on the digital operator and the fault relay is activated 506 515 506 515 5...

Страница 19: ...se s Control board hardware failure Corrective Action Cycle power replace the control board The deviation of the speed reference and speed feedback has exceeded the regulation level A minor fault contact output can be programmed by using the multi function outputs DEV Speed Deviation N A Possible Cause s The load has changed considerably Corrective Action Check the load on the motor verify the pro...

Страница 20: ... replace the digital operator replace the control board CPF01 Com Err OP INV Communication fault between the inverter and the operator has occurred for more than 2 seconds cpf1 Possible Cause s Digital operator cable not securely connected digital operator defective control board defective Corrective Action Check the digital operator cable replace the digital operator replace the control board 505...

Страница 21: ...hardware failure during power up Corrective Action Perform a factory initialization cycle power replace the control board Possible Cause s Noise or spike on the control input terminals Corrective Action Perform a factory initialization cycle power replace the control board 505 Fault Codes Major Fault Motor coasts to a stop the fault is displayed on the digital operator and the fault relay is activ...

Страница 22: ...on the control board input terminals Corrective Action Perform a factory initialization cycle power replace the control board Possible Cause s Noise or spike on the control board input terminals Corrective Action Perform a factory initialization cycle power replace the control board 505 Fault Codes Major Fault Motor coasts to a stop the fault is displayed on the digital operator and the fault rela...

Страница 23: ...tion Remove power to the inverter and connect the option board once more Perform a factory initialization cycle power replace the option board replace the control board Possible Cause s Defective AI 14B option board external input is loading down the option board Corrective Action Remove all inputs to the option board Perform a factory initialization cycle power replace the option board replace th...

Страница 24: ...n Perform a factory initialization cycle power replace the option board replace the control board Possible Cause s Unrecognizable communication or network option board is connected to the control board Corrective Action Remove any option boards and cycle power perform a factory initialization replace the option board replace the control board Fault Codes Major Fault Motor coasts to a stop the faul...

Страница 25: ...d to the control board an option board that is not made for the 515 G5 inverter is attached to the control board Corrective Action Remove power to the inverter and connect the option board once more Perform a factory initialization cycle power replace the option board replace the control board Fault Codes Major Fault Motor coasts to a stop the fault is displayed on the digital operator and the fau...

Страница 26: ...ervolt Uu The DC bus voltage has exceeded the overvoltage trip point while the inverter output is off OV DC Bus Overvolt ou Possible Cause s Single phase condition on the input low input voltage at L1 L2 and L3 Corrective Action Check the three phase input voltage verify setting of L2 05 for GPD515 G5 Possible Cause s High input voltage at L1 L2 and L3 Power factor correction capacitors are being ...

Страница 27: ...ble Cause s Cooling fan s are not working high ambient temperature Corrective Action Check for dirt build up on the fans reduce the ambient temperature around the inverter Possible Cause s An external overheat condition exists connected to one of the multi function input terminals 3 4 5 6 7 or 8 Corrective Action Check for an external condition verify the program parameters Fault Codes Minor Fault...

Страница 28: ...ustomer programmable current detection Response may be selected A minor fault contact output can be programmed by using the multi function outputs Possible Cause s Motor is overloaded Corrective Action Verify the program settings reduce the load on the motor Possible Cause s Motor is overloaded Corrective Action Verify the program settings reduce the load on the motor Fault Codes Minor Fault Opera...

Страница 29: ...command are input simultaneously Corrective Action Check external sequence logic ef0 External fault from serial communication Possible Cause s An external fault condition exists Corrective Action Check for an external condition verify the program parameters EF0 External Fault Fault Codes Minor Fault Operation continues and the digital operator indication blinks The fault relay does not activate 50...

Страница 30: ...xists connected to terminal number 3 Corrective Action Check for an external condition verify the program parameters Possible Cause s An external fault condition exists connected to one of the terminals 4 5 6 7 or 8 Corrective Action Check for an external condition verify the program parameters N A N A Fault Codes Minor Fault Operation continues and the digital operator indication blinks The fault...

Страница 31: ...load on the motor verify the program settings F1 08 PG Overspeed Level and F1 09 PG Overspeed Time Possible Cause s The Pulse Generator feedback wires may be broken or not properly connected to the PG feedback option board torque limit set too low motor shaft locked Corrective Action Check for a broken wire or a loose connection from the Pulse Generator verify the program settings F1 01 PPR and F1...

Страница 32: ...r verify the program settings F1 10 PG Deviate Level F1 11 PG Deviate Time F1 04 PG Deviation Select Possible Cause s Connection is broken master has stopped communicating Corrective Action Check all connections verify all user side software configurations CE Memobus Com Err Transmission error Control data was not received normally when the power supply is turned on Response may be selected ce Fau...

Страница 33: ...d by using the multi function outputs BB Base Block Possible Cause s A baseblock command was accepted at the multi function input terminals 3 4 5 6 7 or 8 Corrective Action Check for an external condition verify the program parameters Fault Codes Minor Fault Operation continues and the digital operator indication blinks The fault relay does not activate 505 506 515 bb ...

Страница 34: ...on ope 1 OPE02 Limit Constant data is out of range 506 digital operator will display OPE06 ope 6 Possible Cause s The control board was replaced and the kVA parameter is set incorrectly Corrective Action Enter the correct kVA setting O2 4 for GPD515 G5 and n115 for GPD506 P5 by referring to the inverter model number Possible Cause s Parameter set above the allowable range Corrective Action Verify ...

Страница 35: ...n option board is installed Remove power to the inverter and connect the option board once more OPE03 Terminal Multi function input selection fault ope 3 Possible Cause s Duplicate functions are selected up down commands or trim control increase decrease are not set simultaneously GPD515 G5 only Speed search from maximum frequency and speed search from set frequency are set simultaneously Correcti...

Страница 36: ...tly installed or missing The control method selection parameter A1 02 is set to 1 or 3 without a feedback board installed Corrective Action Verify that an option board is installed Remove power to the inverter and connect the option board once more OPE07 Analog Selection The multi function analog inputs terminals 14 and 16 are set for the same function Possible Cause s Duplicate functions are sele...

Страница 37: ... in the present control mode Corrective Action Check the modified constants area and verify the set values in parameters H1 01 H1 06 H2 01 H2 03 H3 05 H3 09 H4 01 and H4 04 V F data setting fault 506 digital operator will display OPE10 OPE10 V F Ptrn Setting Possible Cause s The V f parameter settings are not set correctly Corrective Action Check parameters E1 04 E1 11 for the 515 G5 and parameter...

Страница 38: ...frequency proportional gain C6 03 6 and C6 01 C6 02 N A Possible Cause s Parameter setting incorrect Corrective Action Check the program settings and correct the errors Possible Cause s Connection not made properly user software not configured to the proper baud rate or configuration Corrective Action Check all connections verify all user side software configurations CALL Serial Com Call Serial co...

Страница 39: ...he digital operator and the fault relay is not activated CALL SI F G ComCall Serial communication transmission error Communication has not yet been established N A Possible Cause s Connection is broken master has stopped communicating Corrective Action Check all connections verify all user side software configurations 505 506 515 ...

Страница 40: ... you will find the following information Fault code list Terminal function diagram for the GPD 515 G5 Terminal function diagram for the GPD 506 P5 Procedure for power component replacement Thermal compound specifications Power module layout Parts lists not found in the technical manuals ...

Страница 41: ...PP P5G5 03 Troubleshoot Page 41 Rev 06 11 2003 Appendix ...

Страница 42: ...CPF20 Option A D Error N A X 81 CPF21 Option CPU down N A X 82 CPF22 Option Type Err N A X 82 CPF23 Option DPRAM Err N A X 83 DEV Speed Deviation N A X X 19 77 90 E 10 SI F G CPU down N A X 24 73 E 15 SI F G Com Err N A X 23 73 EF External Fault EF X 87 EF0 External Fault EF0 X X 76 87 N A N A EF2 X 76 EF3 External Fault 3 EF3 X X 11 75 88 EF4 External Fault 4 EF4 X X 12 75 88 EF5 External Fault 5...

Страница 43: ...X 93 OPE06 PG Opt Missing N A X 94 OPE07 Analog Selection N A X 94 OPE08 Terminal N A X 95 OPE10 V F Ptrn Setting OPE5 X 95 OPE11 FC On Dly N A X 96 OPR Oper Disconnect OPr X 1E 72 OS Overspeed Det N A X X 18 69 89 OV DC Bus Overvolt OU X X 08 63 84 PF Input Pha Loss SP1 X 1B 68 PGO PG Open N A X X 1A 69 89 PUF DC Bus Fuse Open PUF X 01 65 RH DynBrk Resistor N A X 10 70 RR DynBrk Transistr N A X 0...

Страница 44: ...mple of an OL1 fault being read from a GPD515 G5 with the station address of 02 is shown below PLC GPD 515 G5 02 03 0090 0001 84 14 Station Address H5 01 Read Register Command Fault Code Register CRC High CRC Low Length of of Register TRANSMIT RECEIVE 02 03 02 000B BD 83 Station Address H5 01 Register Requested of Bytes Fault OL1 CRC High CRC Low ...

Страница 45: ...x Ref 0 10V 0 10V 23 0 10V 21 Common 22 Multi function Analog Output Multi function Analog Output 9 10 18 19 20 Multi function Contact Outputs 250Vac 30Vdc 1A 25 26 27 Multi function Open Collector Outputs 48v 50mA B1 B2 The braking circuit is factory installed in the following inverters 230V 1 2 10HP 460V 1 2 20HP Input terminals 1 8 are level sensing type 15 15V 20mA 17 Analog Common 33 15V 20mA...

Страница 46: ...ing jumper J1 on the control board L1 L2 L3 T1 T2 T3 S1 S2 S3 S4 S5 S6 SC Forward Run Multi function Inputs Digital Common Power Supply IM MA MB MC Multi function output 250Vac 30Vdc 1A M1 M2 Multi function output 250Vac 30Vdc 1A Braking resistor 506 P5 FS FV FI FC Main Ref 0 10V AM AC Multi function Output 0 10V Common 2mA maximum B1 B2 Analog Common 2K Aux Ref 4 20mA Analog Supply 15v 2K ...

Страница 47: ... HEAT SINK Incorrect Method for Replacement of Circuit Board Mounted Components Large board mounted components input diodes output IGBT s and power modules are not being correctly installed into small size inverters during repair The components are being soldered to the power board before being mounted to the heat sink ...

Страница 48: ...eplacement of Circuit Board Mounted Components When mounted correctly the power module with thermal compound applied will be in contact with the heatsink The specifications for the thermal compound can be found on the following page POWER BOARD THERMAL COMPOUND 7MBR30NF060 POWER MODULE HEAT SINK ...

Страница 49: ...ents The component must first be mounted to the heat sink The power board should then be installed into the inverter over the top of the components Then the components should be soldered to the power board 1 Mount components to heat sink include thermal compound 2 Install power board over components 3 Solder components to the power board ...

Страница 50: ...r SHIN ETSU SHIN ETSU TOSHIBA CASTALL Description Thermal Compound Thermal Compound Thermal Compound Thermal Compound Material Silicon Grease Silicon Grease Silicon Grease Silicon Grease Appearance White Paste Model Number G746 KS609 YG6260 CASTALL800 Thermal Conductivity 1 6 x 10 cal cm sec C 1 5 x 10 cal cm sec C 2 x 10 cal cm sec C 1 8 x 10 cal cm sec C Temperature Range 50 C 150 C 55 C 200 C 5...

Страница 51: ...t The power module layout for 230V models 0 4kW 5 5kW and 460V models 0 4kW 4 0kW is shown below W V U R S T N E GU GV GW EU EV EW GU GV GW P1 B GB P R S T B U V W P P1 N 1 2 3 4 5 6 7 8 9 10 11 Pin Description 1 GU 2 EU 3 GV 4 EV 5 GW 6 EW 7 GU 8 GV 9 GW 10 GB 11 E ...

Страница 52: ...ut for 230V model 7 5kW and 460V models 5 5kW and 7 5kW is shown below U V W N GW GV GU EW EV EU GZ GY GX P B GDB EX EY EZ W V U B P N 1 2 4 5 7 8 10 11 12 13 14 15 16 Pin Description 1 GW 2 EW 3 Not Used 4 GV 5 EV 6 Not Used 7 GU 8 EU 9 Not Used 10 GX 11 EX 12 GY 13 EY 14 GZ 15 EZ 16 GDB ...

Страница 53: ...PP P5G5 03 Troubleshoot Page 53 Rev 06 11 2003 Power Module Layout The power module layout for 230V 460V 11kW 15kW models is shown below E2 C1 C2E1 G2 E2 E1 G1 C1 G1 E1 G2 E2 C2E1 E2 ...

Страница 54: ...2P2 KNYS7W4R5K R010065 7W 4 5 OHM 10 R14 R22 G5U23P7 P5U23P7 G5U25P5 P5U25P5 KNYS7W3R0K R010066 7W 3 OHM 10 R79 R80 G5U27P5 P5U27P5 R80 R83 G5U2011 P5U2011 RGHS60LS2R2OHMJ R010062 2 2 OHM 10 R1 G5U2015 P5U2015 460V 460V G5U40P4 P5U40P4 G5U40P7 P5U40P7 KNYS10W800K R010067 10W 80 OHM 10 R4 G5U41P5 P5U41P5 G5U42P2 P5U42P2 R12 G5U43P7 P5U43P7 KNYS10W500K R010068 10W 50 OHM 10 R8 R12 G5U44P0 P5U44P0 R8...

Страница 55: ... 60W 2 2 OHM 5 R1 G5U2022 P5U2022 G5U2030 P5U2030 G5U2037 P5U2037 SMR120W R007704 120W 1 OHM 5 R1 G5U2045 P5U2045 G5U2055 P5U2055 G5U2075 P5U2075 SMRW220W R007705 220W 1 OHM 5 R1 460V 460V G5U4018 P5U4018 RGHS80LS6R2OHMJ R010063 80W 6 2 OHM 10 R1 G5U4022 P5U4022 G5U4030 P5U4030 G5U4037 P5U4037 RGHS100LS4R0OHMJ R010078 100W 4 OHM 5 R1 G5U4045 P5U4045 G5U4055 P5U4055 G5U4075 P5U4075 SMRW220W R007705...

Страница 56: ...P2 G5U53P7 P5U53P7 KNYS10W500K R010068 10W 500 OHM 5 R73 R74 G5U5P5 P5U5P5 KNYS10W4ROK RO10069 10W 40 OHM 10 R80 R85 G5U57P5 P5U57P5 G5U5011 P5U5011 RGHS80LS6R20HMJ R0100063 80W 6 2 OHM 5 G5U5015 P5U5015 G5U5018 P5U5018 SMR80WA4904 R007607 80W 4 3 OHM 10 G5U5022 P5U5022 G5U5030 P5U5030 G5U5037 P5U5037 G5U5045 P5U5045 SMR120WA4905 R007608 120W 3 OHM 10 R1 G5U5055 P5U5055 G5U5075 P5U5075 G5U5090 P5U...

Страница 57: ...003011 G5U21P5 P5U21P5 G5U22P2 P5U22P2 HE1AN DC24V POR003013 G5U23P7 P5U23P7 DC 24V MC1 G5U25P5 P5U25P5 HE2AN DC24V POR003014 G5U27P5 P5U27P5 G5U2011 P5U2011 G7J 4A B DC24V POR003012 G5U2015 P5U2015 460V 460V G5U40P4 P5U40P4 G5U40P7 P5U40P7 JC2AF B DC24V POR003015 G5U41P5 P5U41P5 G5U42P2 P5U42P2 G5U43P7 P5U43P7 DC 24V MC1 G5U44P0 P5U44P0 HE2AN DC24V POR003014 G5U45P5 P5U45P5 G5U47P5 P5U47P5 HP 20G...

Страница 58: ... MC003483 200V 70A X MC1 G5U2037 P5U2037 G5U2045 P5U2045 HI 35E2TCU MC003259 250V 200A X MC1 G5U2055 P5U2055 G5U2075 P5U2075 HI 100E2TCU MC003257 200V 190A X MC1 460V 460V G5U4018 P5U4018 HP 20GU MC003260 DC 24V X MC1 G5U4022 P5U4022 HI 15E2TCU MC003274 220V 30A X MC1 G5U4030 P5U4030 G5U4037 P5U4037 HI 20ETCU MC003253 200V 35A X MC1 G5U4045 P5U4045 HI 25ETCU U MC003333 200V 58A X MC1 G5U4055 P5U40...

Страница 59: ...50V 10A X MC1 G5U52P2 P5U52P2 G5U53P7 P5U53P7 HE2AN DC24V POR003014 DC24V 20A 2 POLE X MC1 G5U5P5 P5U5P5 HP 20GU MC003260 DC24V 20A 3A X MC1 G5U57P5 P5U57P5 G5U5011 P5U5011 G5U5015 P5U5015 HP 20GU MC003260 24VDC 20A X MC1 G5U5018 P5U5018 G5U5022 P5U5022 G5U5030 P5U5030 G5U5037 P5U5037 G5U5045 P5U5045 HI 25ETCU U MC003333 200V 58A X MC1 G5U5055 P5U5055 G5U5075 P5U5075 G5U5090 P5U5090 SC 5N UL MC003...

Страница 60: ...P5 INSIDE POWER MODULE PM1 G5U22P2 P5U22P2 SEE OUTPUT TRANSISTOR PARTS LIST G5U23P7 P5U23P7 G5U25P5 P5U25P5 G5U27P5 P5U27P5 TM1 G5U2011 P5U2011 N A N A G5U2015 P5U2015 460V 460V G5U40P4 P5U40P4 G5U40P7 P5U40P7 G5U41P5 P5U41P5 PM1 G5U42P2 P5U42P2 INSIDE POWER MODULE G5U43P7 P5U43P7 SEE OUTPUT TRANSISTOR PARTS LIST G5U44P0 P5U44P0 G5U45P5 P5U45P5 TM1 G5U47P5 P5U47P5 G5U4011 P5U4011 MG50Q1BS11 STR001...

Страница 61: ...nverter Model YEA Code IGBT Number Number Mfg Part Number Number Specifications Designation 600V 600V CIMR CIMR G5U51P5 P5U51P5 G5U52P2 P5U52P2 G5U53P7 P5U53P7 PM1 G5U5P5 P5U5P5 G5U57P5 P5U57P5 G5U5011 P5U5011 MG50Q1BS11 STR001222 1200V 50A TRM4 G5U5015 P5U5015 G5U5018 P5U5018 CM50E3Y 24E STR001218 1200V 50A TRM4 G5U5022 P5U5022 G5U5030 P5U5030 G5U5037 P5U5037 G5U5045 P5U5045 G5U5055 P5U5055 G5U50...

Страница 62: ... 61 MS0650D225N 2 SID000584 50A 2 2MFD SM22 42 62 G5U2055 P5U2055 MS0650D225P 1 SID000583 50A 2 2MFD SM11 31 51 MS0650D225P 2 SID000585 50A 2 2MFD SM12 32 52 MS0650D225N 1 SID000582 50A 2 2MFD SM21 41 61 MS0650D225N 2 SID000584 50A 2 2MFD SM22 42 62 G5U2075 P5U2075 MS0650D225P 1 SID000583 50A 2 2MFD SM111 121 311 321 511 521 MS0650D225P 2 SID000585 50A 2 2MFD SM112 122 312 322 521 522 MS0650D225N ...

Страница 63: ... Code Diode Number Number Mfg Part Number Number Specifications Designation 600V 600V CIMR CIMR G5U51P5 P5U51P5 G5U52P2 P5U52P2 G5U53P7 P5U53P7 G5U5P5 P5U5P5 G5U57P5 P5U57P5 G5U5011 P5U5011 G5U5015 P5U5015 G5U5018 P5U5018 G5U5022 P5U5022 G5U5030 P5U5030 G5U5037 P5U5037 G5U5045 P5U5045 G5U5055 P5U5055 ERG28 14 SID000506 1400V 30A D3 D5 D7 G5U5075 P5U5075 ERG78 14 SID000507 1400V 30A D2 D4 D6 G5U509...

Страница 64: ... R007497 60W 10 OHM 5 R3 8 G5U2037 P5U2037 G5U2045 P5U2045 SMR90WA4748C R007157 90W 10 OHM 5 X2 R3 5 G5U2055 P5U2055 G5U2075 P5U2075 SMR90WA4748M R007697 90W 5 OHM 5 X2 R3 8 460V 460V G5U4018 P5U4018 G5U4022 P5U4022 G5U4030 P5U4030 N A G5U4037 P5U4037 G5U4045 P5U4045 G5U4055 P5U4055 ERF 60WH100 R007497 60W 10 OHM 5 R5 10 G5U4075 P5U4075 G5U4110 P5U4110 SMR90WA4748C R007157 90W 10 OHM 5 X2 R7 9 G5U...

Страница 65: ...tion 600V 600V CIMR CIMR G5U51P5 P5U51P5 G5U52P2 P5U52P2 G5U53P7 P5U53P7 G5U5P5 P5U5P5 G5U57P5 P5U57P5 G5U5011 P5U5011 G5U5015 P5U5015 G5U5018 P5U5018 G5U5022 P5U5022 G5U5030 P5U5030 G5U5037 P5U5037 G5U5045 P5U5045 G5U5055 P5U5055 ERF 60W R007621 60W 10 OHM 5 R7 R12 G5U5075 P5U5075 G5U5090 P5U5090 R9 R11 G5U5110 P5U5110 SMR90W R007672 90W 10 OHM 5 G5U5160 P5U5160 Not Required R12 R14 ...

Страница 66: ... 10 C3 8 G5U2022 P5U2022 G5U2030 P5U2030 G5U2037 P5U2037 G5U2045 P5U2045 DE2110R472K2K C003017 2KV 4700PF C12 29 G5U2055 P5U2055 G5U2075 P5U2075 C17 52 460V 460V G5U4018 P5U4018 C3 8 G5U4022 P5U4022 G5U4030 P5U4030 DMPPT3A335K C006097 1000V 3 3MFD G5U4037 P5U4037 C5 10 G5U4045 P5U4045 G5U4055 P5U4055 G5U4075 P5U4075 DE2110R472K2K C003017 2KV 4700PF C8 25 G5U4110 P5U4110 C15 50 G5U4160 P5U4160 Snub...

Страница 67: ...P5U53P7 G5U5P5 P5U5P5 G5U57P5 P5U57P5 G5U5011 P5U5011 C1NP3B335K YA C006367 1250V 3 3UF 10 C3 C5 G5U5015 P5U5015 G5U5018 P5U5018 C1NP3B225K YA C006366 1250V 2 2UF 10 C7 C9 G5U5022 P5U5022 G5U5030 P5U5030 C1NP3B225K YA C006366 1250V 2 2UF 10 C9 C14 G5U5037 P5U5037 G5U5045 P5U5045 G5U5055 P5U5055 DE2110R472K2K C003017 2KV 4700PF C19 C21 G5U5075 P5U5075 G5U5090 P5U5090 G5U5110 P5U5110 DE2110R472K2K C...

Отзывы: