Fault Codes
Parameter Setting Error
- Inverter can’t run. The fault is displayed
on the digital operator, and the fault relay is not activated.
Multi-function input or multi-function output data
setting error.
OPE08
Terminal
Possible Cause(s):
A multi-function selection has been chosen that is not offered in the
present control mode.
Corrective Action:
Check the “modified constants” area and verify the set values in
parameters H1-01~H1-06, H2-01~H2-03, H3-05, H3-09, H4-01 and H4-04.
V/F data setting fault. 506 digital operator will display
OPE10.
OPE10
V/F Ptrn Setting
Possible Cause(s):
The V/f parameter settings are not set correctly.
Corrective Action:
Check parameters (E1-04 ~ E1-11) for the 515/G5 and parameters
(n012 ~ n018) for the 506/P5. A minimum frequency/voltage value may be set higher than the
maximum frequency/voltage.