Figure 10.13 Locations of Switches
Table 10.8 I/O Terminals and Switches Functions
Position
Switch
Terminal
Function
Default
A
DIP switch S2
-
Enables and disables the MEMOBUS/Modbus communications
termination resistor.
OFF
B
Jumper Switch S5
FM, AM
Sets terminals FM and AM to voltage or current output.
FM: V (voltage output)
AM: V (voltage output)
C
DIP switch S1-1
A1
Sets the input signal type (voltage/current).
V (voltage input)
DIP switch S1-2
A2
Sets the input signal type (voltage/current).
I (current input)
DIP switch S1-3
A3
Sets the input signal type (voltage/current).
V (voltage input)
D
DIP switch S4
A3
Sets MFAI or PTC input.
AI (analog input)
◆
Control I/O Connections
This section gives information about the settings for the listed control circuit I/O signals.
•
MFDI (terminals S1 to S8)
•
Pulse train output (terminal MP)
•
MFAI (terminals A1 to A3)
•
PTC input (terminal A3)
•
MFAO (terminals FM, AM)
•
MEMOBUS/Modbus communications (terminals D+, D-, AC)
■
Pulse Train Output
You can use pulse train monitor output terminal MP for sourcing mode or for sinking mode.
NOTICE
Correctly connect peripheral devices. Incorrect installation can cause damage to the drive and connected circuits.
•
Use for sourcing mode
The load impedance changes the voltage level of the pulse train output signal.
Load Impedance
R
L
(k
Ω
)
Output Voltage
V
MP
(V)
1.5 kΩ or more
5 V or more
4.0 kΩ or more
8 V or more
10 kΩ or more
10 V or more
Note:
Use the formula in
to calculate the necessary load resistance (kΩ) to increase output voltage V
MP
(V).