130
YASKAWA
TOEPC71061737D GA800 DRIVE INSTALLATION & PRIMARY OPERATION
部件名称
有害物质
铅
(Pb)
汞
(Hg)
镉
(Cd)
六价铬
(Cr(VI))
多溴联苯
(PBB)
多溴二苯醚
(PBDE)
铝压铸
×
○
○
○
○
○
本表格依据
SJ/T 11364
的规定编制。
○
:
表示该有害物质在该部件所有均质材料中的含量均在
GB/T 26572
规定的限量要求以下。
×
:
表示该有害物质至少在该部件的某一均质材料中的含量超出
GB/T 26572
规定的限量要求。
(注) 本产品符合欧盟
RoHS
指令。上表中的
“
×
”
表示含有欧盟
RoHS
指令豁免的有害物质。
16
Safe Disable Input
This section gives precautions to support the Safe Disable input. Contact Yaskawa for more information.
The safety function complies with the standards shown in
.
Table 16.1 Applied Safety Standards and Unified Standards
Safety Standards
Unified Standards
Functional Safety
IEC/EN 61508 (SIL3)
IEC/EN 62061 (SILCL3)
IEC/EN 61800-5-2 (SIL3)
Machine Safety
ISO/EN ISO 13849-1:2015 (Cat.3, PL e)
EMC
IEC/EN 61000-6-7
Note:
•
SIL = Safety Integrity Level.
•
SILCL = SIL Claim Limit.
◆
Safe Disable Specifications
The Safe Disable input provides the stop function that complies with
“
Safe Torque Off
”
as specified by IEC/EN
61800-5-2. The Safe Disable input meets the requirements of EN ISO 13849-1 and IEC/EN 61508. It also has a safety
status monitor to detect safety circuit errors.
When you install the drive as a component in a system, you must make sure that the system complies with the
applicable safety standards.
Refer to
for safety function specifications.
Table 16.2 Safe Disable Specifications
Item
Description
Input/Output
•
Input: 2
Safe Disable input (H1, H2)
Signal ON level: 18 Vdc to 28 Vdc
Signal OFF level: -4 Vdc to +4 Vdc
•
Output: 1
MFDO safety monitor output for external device monitor (EDM)
Response time from when the input opens to when the drive output stops
3 ms or less
Response time from when the H1 and H2 terminal inputs open to when the EDM
signal operates
20 ms or less
Failure probability
Less frequent operation request mode
PFD = 4.65E
-6
Frequent operation request mode or
continuous mode
PFH = 1.11E
-9
Performance level
The Safe Disable input complies with the performance level requirements of EN ISO 13849-1.
HFT (hardware fault tolerance)
N = 1
Type of subsystem
Type B