Wiring Control Circuit Terminals
2
-
21
Control Circuit Terminal Functions
The functions of the control circuit terminals are shown in
Table 2.11
. Use the appropriate terminals for the
correct purposes.
Table 2.11 Control Circuit Terminals with default settings
Type
No.
Signal Name
Function
Signal Level
Digital
input
signals
S1
Forward run/stop command
Forward run when ON; stopped when OFF.
24 VDC, 8 mA
Photocoupler isolation
S2
Reverse run/stop command
Reverse run when ON; stopped when OFF.
S3
External fault input
*1
Fault when ON.
Functions are
selected by set-
ting H1-01 to
H1-05.
S4
Fault reset
*
Reset when ON
S5
Multi-step speed reference
1
*1
(Master/auxiliary switch)
Auxiliary frequency ref-
erence when ON.
S6
Multi-step speed reference
2
*1
Multi-step setting 2 when
ON.
S7
Jog frequency reference
*1
Jog frequency when ON.
SC
Digital input common
–
–
SN
Digital Input Neutral
–
–
SP
Digital Input Power Supply
+24VDC power supply for digital inputs
24 VDC, 250 mA max.
*2
Analog
input
signals
+V
15 V power output
15 V power supply for analog references
15 V
(Max. current: 20 mA)
A1
Frequency reference
0 to +10 V/100%
0 to +10 V(20 k
Ω
)
A2
Multi-function analog input
4 to 20 mA/100%
0 V to +10 V/100%
0 to 20 mA/100%
Function is
selected by set-
ting H3-09.
4 to 20 mA(250
Ω
)
0 V to +10 V(20k
Ω
)
0 to 20 mA (250
Ω
)
AC
Analog reference common
–
–
E(G)
Shield wire, optional ground
line connection point
–
–
Se-
quence
output
signals
M1
Running signal
(1NO contact)
Operating when ON.
Multi-function
contact outputs
Dry contacts
Contact capacity:
1 A max. at 250 VAC
1 A max. at 30 VDC
*3
M2
M3
Zero speed
Zero level (b2-01) or
below when ON
M4
MA
Fault output signal
Fault when CLOSED across MA and MC
Fault when OPEN across MB and MC
–
MB
MC
Analog
output
signals
FM
Multi-function analog output
(frequency output)
0 to +10 V/100% fre-
quency
Multi-function
analog output 1
0 to +10 V max. ±5%
2 mA max.
AC
Analog common
–
AM
Multi-function analog output
(current monitor)
5 V/Inverter's rated cur-
rent
Multi-function
analog output 2
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Содержание E7 Drive
Страница 3: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 19: ...XVIII Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 37: ...1 18 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 75: ...3 12 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 87: ...4 12 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 265: ...7 18 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 287: ...10 12 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 288: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...