User Constant Tables
5
-
27
Multi-function Contact Outputs: H2
Multi-function Contact Output Functions
19
PI control disable (ON: PI control disabled)
6-86
1B
Constants write enable (ON: All constants can be written-in. OFF: All constants are write pro-
tected.)
6-109
1C
Trim control increase (ON: d4-02 frequency is added to analog frequency reference.)
6-58
1D
Trim control decrease (ON: d4-02 frequency is subtracted from analog frequency reference.)
6-58
1E
Analog frequency reference sample/hold
6-59
20 to 2F
External fault
Input mode: NO contact/NC contact, Detection mode: Normal/during operation
6-62
30
PI control integral reset (reset when reset command is input or when stopped during PI control)
6-86
31
PI control integral hold (ON: Hold)
6-86
34
PI soft starter disable (ON: disabled)
6-86
35
PI input characteristics switch
6-86
36
Operation Source Option/Inverter selection 2 (ON: inverter settings)
6-60
60
Motor preheat command (ON: Performs motor preheat)
6-14
61
External search command 1 (ON: Speed search from maximum output frequency)
6-40
62
External search command 2 (ON: Speed search from set frequency)
6-40
64
External speed search command 3
6-39
65
KEB (deceleration at momentary power loss) command (NC contact)
–
66
KEB (deceleration at momentary power loss) command (NO contact)
–
67
Communications test mode
6-81
68
High-slip braking (HSB)
6-101
69
Jog Frequency 2
6-8
6A
Drive enable (NC, ON: Drive enabled, OFF: Drive disabled
6-53
6B
Operation Source Communication/Inverter selection (ON: RS-422/485 port)
6-60
6C
Operation Source Communication/Inverter selection 2 (ON: inverter settings)
6-60
6D
AUTO mode selection (ON: AUTO mode active)
6-61
6E
HAND mode selection (ON: HAND mode active)
6-61
6F
Maintenance Mode
–
70
Bypass Drive Enable
6-53
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
MEMO-
BUS
Register
Page
H2-01
Terminal M1-M2
function selection
Multi-function contact
output 1
0 to 38
0
No
A
40BH
–
H2-02
Terminal M3-M4
function selection
Multi-function contact
output 2
0 to 38
1
No
A
40CH
–
Setting
Value
Function
Page
0
During run (ON: run command is ON or voltage is being output)
6-63
1
Zero-speed
6-64
Setting
Value
Function
Page
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Содержание E7 Drive
Страница 3: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 19: ...XVIII Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 37: ...1 18 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 75: ...3 12 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 87: ...4 12 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 265: ...7 18 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 287: ...10 12 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 288: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...