5
-4
User Constants Setable in Quick Programming Mode
The minimum user constants required for Inverter operation can be monitored and set in quick programming
mode. The user constants displayed in quick programming mode are listed in the following table. These, and
all other user constants, are also displayed in advanced programming mode.
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
MEMO-
BUS
Regis-
ter
A1-00
Language selec-
tion for Digital
Operator display
Used to select the language displayed on
the Digital Operator JVOP-160 only.
0: English
1: Japanese
2: German
3: French
4: Italian
5: Spanish
6: Portuguese
This constant is not changed by the initial-
ize operation.
0 to 6
0
Yes
A
100H
b1-01
Reference
source selection
Sets the frequency reference input
method.
0: Digital Operator
1: Control circuit terminal (analog input)
2: MEMOBUS communications
3: Option Card
0 to 3
1
No
Q
180H
b1-02
RUN command
source selection
Sets the run command input method
0: Digital Operator
1: Control circuit terminal (digital multi-
function inputs)
2: MEMOBUS communications
3: Option Card
0 to 3
1
No
Q
181H
b1-03
Stopping
method selection
Select stopping method when stop com-
mand is input.
0: Deceleration to stop
1: Coast to stop
2: DC braking stop (Stops faster than
coast to stop, without regenerative
operation.)
3: Coast to stop with timer (Run
commands are disregarded during
deceleration time.)
0 to 3
0
No
Q
182H
b1-04
Prohibition of
reverse opera-
tion
0: Reverse enabled
1: Reverse disabled
2: Output Phase Rotation (both rotational
directions are enabled)
3: Output Phase Rotation with Reverse
prohibited.
0 to 3
0
No
A
183H
b4-01
Timer function
ON-delay time
Sets the timer function output ON-delay
time (dead time) for the timer function
input, in 1-second units.
Enabled when a timer function is set in
H1-
and H2-
.
0.0 to
3000.0
0.0 s
No
A
1A3H
b5-01
PI control mode
selection
0: Disabled
1: Enabled
3: PI control enabled (frequency reference
+ PI output)
0, 1, 3
0
No
A
1A5H
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Содержание E7 Drive
Страница 3: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 19: ...XVIII Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 37: ...1 18 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 75: ...3 12 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 87: ...4 12 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 265: ...7 18 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 287: ...10 12 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 288: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...