YASKAWA
SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
491
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
F5-07
(039F)
Terminal M1-M2
Function Select
Sets the function of terminal M1-M2 on the DO-A3 option by the setting value for the
multi-function digital output (0 - 1FF). Set
F5-09 = 2 [DO-A3 Output Mode Selection =
Programmable (F5-01 to F5-08)]
to enable this function.
F
(0 - 1FF)
F5-08
(03A0)
Terminal M3-M4
Function Select
Sets the function of terminal M3-M4 on the DO-A3 option. Set
F5-09 = 2 [DO-A3
Output Mode Selection = Programmable (F5-01 to F5-08)]
to enable this function.
F
(0 - 1FF)
F5-09
(03A1)
DO-A3 Output Mode
Selection
Sets the output mode of signals from the DO-A3 option.
0 : Predefined Individual Outputs
1 : Binary Output
2 : Programmable (F5-01 to F5-08)
0
(0 - 2)
◆
F6: Communication Options
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
F6-01
(03A2)
Communication Error
Selection
Selects the operation of the drive when the drive detects
bUS [Option Communication
Error]
.
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
4 : Alarm (Run at
d1-04
)
5 : Alarm - Ramp Stop
1
(0 - 5)
F6-02
(03A3)
Comm External Fault
(EF0) Detect
Sets the conditions at which
EF0 [Option Card External Fault]
is detected.
0 : Always Detected
1 : Detected during RUN Only
0
(0, 1)
F6-03
(03A4)
Comm External Fault
(EF0) Select
Selects the operation of the drive when the drive detects
EF0 [Option Card External
Fault]
.
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
1
(0 - 3)
F6-04
(03A5)
bUS Error Detection
Time
Sets the delay time for the drive to detect
bUS [Option Communication Error]
.
Note:
When you install an option card in the drive, the parameter value changes to 0.0 s.
2.0 s
(0.0 - 5.0 s)
F6-06
(03A7)
Torque Reference/Limit
by Comm
Sets the function that enables and disables the torque limit received from the
communication option.
0 : Disable
1 : Enabled
0
(0, 1)
F6-07
(03A8)
Multi-Step Ref @
NetRef/ComRef
Sets the function that enables and disables the multi-step speed reference when NetRef
(communication option card) or ComRef (MEMOBUS/Modbus communications) are
the frequency reference source.
0 : Disable Multi-Step References
1 : Enable Multi-Step References
0
(0, 1)
F6-08
(036A)
Comm Parameter Reset
@Initialize
Sets the function to initialize
F6-xx and F7-xx parameters
when the drive is initialized
with
A1-03 [Initialize Parameters]
.
0 : No Reset - Parameters Retained
1 : Reset Back to Factory Default
0
(0, 1)
F6-10
(03B6)
CC-Link Node Address
Sets the node address for CC-Link communication. Restart the drive after you change
the parameter setting.
Note:
Be sure to set a node address that is different than all other node addresses. Do not
set this parameter to
0
. Incorrect parameter settings will cause
AEr [Station Address
Setting Error]
errors and the L.ERR LED on the option will come on.
0
(0 - 64)
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...