670
YASKAWA
SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
The multi-step speed reference (2-step speed to 8-step speed references) and the Jog Frequency Reference (JOG
command) are disabled when NetRef or ComRef is selected as the frequency reference source.
1 : Enable Multi-Step References
The multi-step speed reference (2-step speed through 8-step speed references) and the Jog Frequency Reference
(JOG command) are enabled, and the frequency reference can be changed when NetRef or ComRef is selected as
the frequency reference source.
■
F6-08: Comm Parameter Reset @Initialize
No.
(Hex.)
Name
Description
Default
(Range)
F6-08
(036A)
Comm Parameter Reset
@Initialize
Sets the function to initialize
F6-xx and F7-xx parameters
when the drive is initialized with
A1-03
[Initialize Parameters]
.
0
(0, 1)
0 : No Reset - Parameters Retained
1 : Reset Back to Factory Default
Note:
When you use
A1-03
to initialize the drive, this setting will not change.
■
F6-10: CC-Link Node Address
No.
(Hex.)
Name
Description
Default
(Range)
F6-10
(03B6)
CC-Link Node Address
Sets the node address for CC-Link communication. Restart the drive after you change the
parameter setting.
0
(0 - 64)
Note:
Be sure to set a node address that is different than all other node addresses. Do not set this parameter to
0
. Incorrect parameter settings
will cause
AEr [Station Address Setting Error]
errors and the L.ERR LED on the option will come on.
When the only drive is connected, you can connect a maximum of 42 nodes. Follow these rules to connect devices
that are not drives:
•
{(1 × a) + (2 × b) + (3 × c) + (4 × d)} ≤ 64
(a: number of units that occupies 1 node, b: number of units that occupies 2 nodes, c: number of units that
occupies 3 nodes, d: number of units that occupies 4 nodes)
•
{(16 × A) + (54 × B) + (88 × C)} ≤ 2304
(A: number of remote I/O nodes (64 max.), B: number of remote device nodes (42 max.), C: number of local
nodes (26 max.))
■
F6-11: CC-Link Communication Speed
No.
(Hex.)
Name
Description
Default
(Range)
F6-11
(03B7)
CC-Link Communication
Speed
Sets the communication speed for CC-Link communication. Restart the drive after you change the
parameter setting.
0
(0 - 4)
0 : 156 kbps
1 : 625 kbps
2 : 2.5 Mbps
3 : 5 Mbps
4 : 10 Mbps
■
F6-14: BUS Error Auto Reset
No.
(Hex.)
Name
Description
Default
(Range)
F6-14
(03BB)
BUS Error Auto Reset
Sets the automatic reset function for
bUS [Option Communication Errors]
.
0
(0, 1)
0 : Disable
1 : Enabled
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...