EtherNet/IP 3-3
Speed and Torque Control Output Instance 22 (16h)
Note:
1
Becomes torque limit in torque mode
2
F7U, G7U and G5M in FVC mode only
Run Forward:
Forward RUN Command
Run Reverse:
Reverse RUN Command
Fault Reset:
Fault Reset Command
Speed Reference:
RPM when o1-03 = (2 ~ 39)
Torque Reference:
Percent of rated torque - (F7U, G7U and G5M Closed-loop flux vector mode (FVC) only)
Extended Speed and Torque Control Output Instance 23 (17h)
Note:
1
Becomes torque limit in torque mode
2
F7U, G7U and G5M in FVC mode only
Run Forward:
Forward RUN Command
Run Reverse:
Reverse RUN Command
Fault Reset:
Fault Reset Command
Net Control:
Parameter b1-02
0 - 1 transition sets b1-02 = 3
1 - 0 transition sets b1-02 to previous value
Net Reference:
Parameter b1-01
0 - 1 transition sets b1-01 = 3
1 - 0 transition sets b1-01 to previous value
Speed Reference:
RPM when o1-03 = (2 ~ 39)
Torque Reference:
Percent of rated torque - (F7U, G7U and G5M in Closed-loop flux vector mode (FVC) only)
Output
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Instance
0
-
-
-
-
-
Fault
Reset
-
Run
Forward
22
1
-
2
Speed Reference
1
(Low Byte) [scaled by parameter o1-03]
3
Speed Reference
1
(High Byte) [scaled by parameter o1-03]
4
Torque Reference
2
(Low Byte) [0.1%]
5
Torque Reference
2
(High Byte) [0.1%]
Output
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Instance
0
-
Net
Reference
Net
Control
-
-
Fault
Reset
Run
Reverse
Run
Forward
23
1
-
2
Speed Reference
1
(Low Byte) [scaled by parameter o1-03]
3
Speed Reference
1
(High Byte) [scaled by parameter o1-03]
4
Torque Reference
2
(Low Byte) [0.1%]
5
Torque Reference
2
(High Byte) [0.1%]