3 Electrical Installation
YASKAWA Europe
TOEP C710606 75B - AC Drive V1000 IP66 - Quick Start Guide
EN 15
• Do not use phase correction capacitors.
• If using a contactor between the drive and motor, it should never be operated when the drive is outputting a voltage. Operating while there is
voltage output can cause large peak currents, thus tripping the over current detection or damage the drive.
Ground Connection
Take the following precautions when grounding the drive.
• Never share the ground wire with other devices such as welding machines, etc.
• Always use a ground wire, that complies with electrical equipment technical standards. Keep ground wires as short as possible. Leakage current
is caused by the drive. Therefore, if the distance between the ground electrode and the ground terminal is too long, potential on the ground
terminal of the drive will become unstable.
• Make sure the ground conductor complies with technical standards and local safety rules. The drive has an EMC filter installed and the leakage
current exceeds 3.5 mA. Therefore according to IEC61800-5-1, a protective earthing conductor with a cross section of at least 10 mm
2
(Cu) or 16
mm
2
(Al) must be used, or automatic power supply interruption in case of discontinuity of the protective earthing conductor must be provided.
• When using more than one drive, do not to loop the ground wire.
Control Circuit Wiring Precautions
Consider the following precautions for wiring the control circuits.
• Separate control circuit wiring from main circuit wiring and other high-power lines.
• Separate wiring for control circuit terminals MA, MB, MC (contact output) from wiring to other control circuit terminals.
• For external control power supply use a UL Listed Class 2 power supply.
• Use twisted-pair or shielded twisted-pair cables for control circuits to prevent operating faults.
• Connect only Digital Operator JVOP-180 (LCD), JVOP-182(LED) or JVOP-181 (USB Copy Unit) to external RJ45 connector on drives model
code CIMR-...-0081. Do not connect any other device to the RJ45 connnector.Drive or external device may be damaged.
• Drives model code CIMR-...0080 can be connected to PC by using JVOP-181(USB Copy Unit). Use the RJ45 connector where the Digital
Operator is connected.
• Ground the cable shields with the maximum contact area of the shield and ground.
• Cable shields should be grounded on both cable ends.
• If flexible wires with ferrules are connected they might fit tightly into the terminals. To disconnect them, grasp the wire end with a pair of pliers,
release the terminal using a straight-edge screw driver, turn the wire for about 45
and pull it gently out of the terminal. For details, refer to the
Technical Manual. Use this procedure for removing the wire link between HC, H1 and H2 when the Drive Disable function is utilized.
Main Circuit Terminals
Control Circuit Terminals
The figure below shows the control circuit terminal arrangement. The drive is equipped with screwless terminals.
There are three DIP switches, S1 to S3, located on the terminal board
Control Circuit Terminal Functions
Terminal
Type
Function
L1, L2, L3
(located at the built-in EMC filter)
Main circuit power supply input
Connects line power to the drive.
Drives with single-phase 200 V input power have no L3 terminal.
U/T1, V/T2, W/T3
Drive output
Connects to the motor.
B1, B2
Braking resistor
For connecting a braking resistor.
+1, +2
DC reactor connection
Linked at shipment. Remove the link to install a DC choke.
+1, –
DC power supply input
For connecting a DC power supply.
(2 terminals)
Ground Terminal, (green colored
screws)
SW1
Switches analog input A2 between voltage and current input
SW2
Enables or disables the internal RS422/485 comm. port terminal resistance.
SW3
Used to select sourcing (PNP)/sinking (NPN, default) mode for the digital inputs (PNP requires external 24 Vdc power supply)
Type
No.
Terminal Name (Signal)
Function (Signal Level), Default Setting
Multi-Function
Digital Inputs
S1
to
S6
Multi-function digital input 1 to 6
Photocoupler inputs, 24 Vdc, 8 mA
Note: Drive preset to sinking mode (NPN). When using source mode, set DIP switch
S3 to “SOURCE” and use an external 24 Vdc (±10%) power supply.
SC
Multi-function input common
Sequence common
S1 S2 S3 S4 S5 S6 SC HC H1 H2 RP
R+ R- S+ S- IG
P1 P2 PC A1 A2 +V AC AM AC MP
MA MB MC
S1
S2
S3
Use a straght-edge screwdriver
with a blade width of max 2.5 mm
and a thickness of max 0.6 mm to
release the terminals