3  Electrical Installation

YASKAWA Europe 

TOEP C710606 75B - AC Drive V1000 IP66 - Quick Start Guide

EN  13

3

Electrical Installation

The figure below shows the main and control circuit wiring.

<1> Single-phase units do not have a L3 terminal.

<2> These terminals can be used to disable the drive output. Other than in V1000 standard drives they can NOT be used to perform safe stop according to EN60204-1 (Function 

is in preparation. Contact your sales representative or YASKAWA for details).

Power 

Supply

L1

L2

L3

S1

S2

S3

S4

S5

S6

B1

+1

+2

B2

L1

L2

L3

U/T1

V/T2

W/T3

24 V

0 V

SINK

SOURCE

MA

P1

MB

MC

+

24 V 8 mA

M

U

V

W

SC

P2

MP

AM

AC

PC

IG

R

+

R

S

+

S

H2

RP

+V

A1

A2

AC

2 k

Ω

HC

H1

DC reactor 

(option)

Filter

Fuses

Main 

Switch

Forward/Stop

Reverse/Stop

External Fault

Fault Reset

Multi-speed 1

Multi-speed 2

Multi-function 

digital inputs

(default setting)

Link

Thermal 

relay

Braking 

resistor

(opt)

V1000 IP66

Ground

Multi-function relay output
250 Vac / 30 Vdc (10 mA to 1A)
(default setting)

Fault

During run

Frequency agree

Photocoupler 
common

Multi-function 
photo-
coupler output
48 Vdc, 2 to 50 mA
(default setting)

DIP
switch S3

Shielded ground 
terminal

Pulse Input
(max. 32kHz)

Multi-function analog input 1
0 to 10 V (20 k

Ω

)

Multi-function analog input 2
0 to 10 V (20 k

Ω

) or

0/4 to 20 mA (250 

Ω

)

Analog input power supply
+10.5 Vdc, max. 20 mA

Multi-function pulse / analog inputs
(default: frequency reference)

Drive Disable  

inputs

Monitor outputs
(default setting)

Analog output
0 to +10 Vdc (2mA)
(Output frequency)

Pulse train output
(max. 32 kHz)
(Output frequency)

Terminal resistance
(120 

Ω

, 1/2 W)

Memobus comm.
RS-485/422
max. 115 kbps

Shielded 

Cable

Symbols:

Use twisted pair cables.

Use shielded twisted pair cables.

Indicates the IP66 enclosure.

Indicates a main circuit terminal. 

Indicates a control circuit terminal.

<1>

<2>

Содержание CIMR-VC*****H**-00 series

Страница 1: ...O TOEP C710606 75B Type CIMR VC H 00 Models 200 V Class Single Phase Input 0 1 to 3 0 kW 400 V Class Three Phase Input 0 2 to 18 5 kW To properly use the product read this manual thoroughly and retain...

Страница 2: ...n permission of Yaskawa No patent liability is assumed with respect to the use of the information contained herein Moreover because Yaskawa is constantly striving to improve its high quality products...

Страница 3: ...00 IP66 Quick Start Guide Table of Contents 1 GENERAL INFORMATION AND SAFETY INSTRUCTIONS 4 2 MECHANICAL INSTALLATION 8 3 ELECTRICAL INSTALLATION 13 4 KEYPAD OPERATION 17 5 START UP 19 6 PARAMETER TAB...

Страница 4: ...eries IP66 Type drives Receiving Please perform the following tasks after receiving the drive Inspect the drive for damage If the drive appears damaged upon receipt contact your supplier Verify receip...

Страница 5: ...ious injury YASKAWA is not responsible for any modification of the product made by the user This product must not be modified Never submerge this product in water Using this product in water can damag...

Страница 6: ...ding to IEC 60755 Sudden Movement Hazard Stay clear of the motor during rotational Auto Tuning The motor may start operating suddenly During automatic starting of equipment the machine may start movin...

Страница 7: ...issing parts Prevent moisture and other solvents from entering the drive enclosure Failing to do so can damage the drive or considerably shorten its expected performance life Install adequate branch c...

Страница 8: ...od possible with other models Environment Conditions Installation Area Indoors Ambient Temperature 10 C to 40 C Drive reliability improves in environments without wide temperature fluctuations Storage...

Страница 9: ...efore the front cover can be removed NOTICE Never disassemble the protective case that encloses the drive The case is constructed as a single continuous piece that includes the heatsink Attempting to...

Страница 10: ...drive NOTICE RJ45 connector on drives with model code CIMR 0081 is meant to connect an external digital operator JVOP 180 LCD JVOP 182 LED with recommended cable YASKAWA part No 72606 WV003 or JVOP 1...

Страница 11: ...utside may allow water or oil into the drive and damage components Cable Glands Specifications and Model Numbers YASKAWA recommends using SKINTOP cable glands by Lapp Kabel for use with V1000 Series I...

Страница 12: ...Wiring glands are plastic Part No Model PG Size Wrench Size SW mm A mm B mm C mm D mm Body 53015140 STR 16 16 27 44 10 53015040 ST 16 Locknut 53019040 GMP GL 16 16 30 33 6 Part No Model PG Size Wrench...

Страница 13: ...d 2 Multi function digital inputs default setting Link Thermal relay Braking resistor opt V1000 IP66 Ground Multi function relay output 250 Vac 30 Vdc 10 mA to 1A default setting Fault During run Freq...

Страница 14: ...switch with a large capacity power supply transformer over 600 kVA Wiring the Main Circuit Output Consider the following precautions for the output circuit wiring Do not connect any other load than a...

Страница 15: ...e CIMR 0080 can be connected to PC by using JVOP 181 USB Copy Unit Use the RJ45 connector where the Digital Operator is connected Ground the cable shields with the maximum contact area of the shield a...

Страница 16: ...rive output disabled time from input open to drive output switch off is less than 1 ms Both Closed Normal operation H2 Drive Disable Input 2 Multi Function Relay Output MA N O fault Digital relay outp...

Страница 17: ...e LOCAL mode The Stop LED is on when the drive is not operating the motor flashes during deceleration at a fast stop or stop by interlock operation is off during run deceleration to stop or when the f...

Страница 18: ...urrent Output Voltage Monitor Display Verify Menu Setup Mode Parameter Setting Mode Auto Tuning DRV LED is on A Run command will start the motor The Monitor Displays are used to read out drive data li...

Страница 19: ...arameter settings are unknown Open Loop Vector Control OLV A1 02 2 General variable speed applications Applications requiring high precision high speed control PM Open Loop Vector Control A1 02 5 Dera...

Страница 20: ...ility OL2 150 of drive rated current for 60 s 120 of drive rated current for 60 s L3 02 Stall Prevention during Acceleration 150 120 L3 06 Stall Prevention during Run 150 120 Default carrier frequency...

Страница 21: ...n of each analog input can be assigned in the H3 parameters The default setting of both inputs is Frequency bias Input A1 is set for 0 to 10V input and A2 is set for 4 20 mA input The addition of both...

Страница 22: ...to 0 00 seconds Acceleration Deceleration C1 01 Accel Time 1 Sets the acceleration time 1 from 0 to the max output frequency C1 02 Decel Time 1 Sets the deceleration time 1 from the max output frequen...

Страница 23: ...blower cooled motor 3 Vector motor L1 02 Motor Overload Prot Time Sets the motor overload protection time in min Normally no change is necessary Stall Prevention L3 01 Stall Prevention Selection durin...

Страница 24: ...at occurred through the fourth most recent fault U3 05 to U3 08 Accumulated operation time at the most recent fault through the fourth most recent fault U3 09 to U3 14 Lists the fifth most recent faul...

Страница 25: ...Replace any broken parts Reduce the carrier frequency Drive Disable Both Drive Disable inputs are open The drive output is safely disabled and the motor can not be started Check why the upper control...

Страница 26: ...tting range Set parameters to the proper values oPE03 A contradictory setting is assigned to multi function contact inputs H1 01 through to H1 06 The same function is assigned to two inputs this exclu...

Страница 27: ...he acceleration time C1 01 If possible disconnect the load Er 12 Current detection error One or all output phases are lost Current is either too low or exceeds the drives rating The current sensors ar...

Страница 28: ...nt Cover on page 9 3 Make sure the charge LED on the drive has gone off 4 Unplug the internal fan cable connector 3 wires right side connector from the drive 5 Unmount the stirring fan holding bracket...

Страница 29: ...apacitors to discharge 2 Remove the IP66 front cover as described in Removing the Front Cover on page 9 3 Make sure the charge LED on the drive has gone off 4 Unplug the external fan cable connector 2...

Страница 30: ...8 Maintenance EN 30 YASKAWA Europe TOEP C710606 75B AC Drive V1000 IP66 Quick Start Guide...

Страница 31: ...re given on the bottom of the back cover Date of Publication Rev No Section Revised Contents October 2010 First Edition June 2013 2 Front Back Covers Content Pages Cover Revision including Logo Update...

Страница 32: ...ct to change without notice for ongoing product modifications and improvements 2013 YASKAWA EUROPE GmbH All rights reserved EUROPEAN HEADQUARTERS YASKAWA EUROPE GmbH Hauptstra e 185 65760 Eschborn Ger...

Отзывы: