APPENDIX 3 TYPICAL CONNECTION DIAGRAM
3.1
BRAKING RESISTOR UNIT
For Model CIMR-SSA20P4 to -SSA27P5 (200 V Class 0.4 to 7.5 kW),
Models CIMR-SSA40P4 to -SSA4015 (400 V Class 0.4 to 15 kW)
©
¨
1
DC Reactor
(Option)
[
Overload Relay Trip Contact
Braking Resistor Unit
]
VS-686SS5
MCCB
3-Phase
Power Supply
200 to 230 V
50/60 Hz
or
380 to 460 V
50/60 Hz
R
MC
R (L1)
S
S (L2)
T
T (L3)
:
400/200 V
THRX OFF
ON
MC
SA
Overload Relay Trip Contact
of Braking Resistor Unit
1
2
MC
TRX
TRX
20 18
Fault
Contact
Forward Run/Stop
Reverse Run/Stop
Factory
Setting
External Fault
Fault Reset
Multi-step Speed Setting 1
(Master/Aux Change)
Multi-step Speed
Setting 2
Jog Reference
External Baseblock
Use sequencer to break
power supply side on
overload relay trip contact
of braking resistor unit.
¨
2
B1
B2
SA
SA
THRX
2 k
Ω
2 k
Ω
0 to +10 V
4 to 20 mA
P
0 to +10 V
P
0 V
P
External
Speed
Reference
Multi-function Open
Collector Output
48 V 50 mA or less
Multi-function
Output Common
27
Open Collector 2
(Speed Agree Signal
at Factory Setting)
26
Open Collector 1
(Zero Speed Signal at
Factory Setting)
25
Multi-function Contact Output
250 VAC 1 A or less
30 VDC 1A or less
(Signal during Running at Factory
Setting)
10
9
20
19
Fault Contact Output
250 VAC 1 A or less
30 VDC 1 A or less
18
+
AM
23
+
−
Multi-function Analog Output
-10 to +10V 2mA
(Output Current at Factory
Setting)
21
22
SM
−
Analog
Monitor 1
(12)
Multi-function Analog Output
-10 to +10 V 2mA
(Rotation Speed at Factory
Setting)
U (T1)
V (T2)
W (T3)
Motor
M
Ground (200V Class : 100
Ω
or less
400V Class : 10
Ω
or less)
:
The transformer is not necessary for 200V class.
1 Forward Run when
CLOSED
2 Reverse Run when
CLOSED
3
4
5
6
7
8
Multi-function
Contact Input
11
Sequence Common
Terminal (0V)
12
Shield Sheath
Connection Terminal
15 Speed Setting Power
15V 20mA
13 Master Speed Ref.
0 to 10V (20k
Ω
)
14 Master Speed Ref.
4 to 20mA (250
Ω
)
16 Multi-function Analog Input
0 to 10V (20k
Ω
)
0 V
33 Speed Setting Power Supply
-15V 20mA
17 (Aux Speed Ref. at
Factory Setting)
1
2
B
P
MC
Analog
Monitor 2
18
[
When installing a DC reactor (option), remove the common bar between
¨
1 and
¨
2 terminals
(provided as standard) and connect a DC reactor with the terminals.
]
When using the braking resistor unit, set constant L3-01 to “0” (overvoltage prevention selection
is disabled). If it is not changed, the inverter may not stop within set decel time.
Short-circuit
Bar
20