6.5 Regenerative Unit Replacement
124
YASKAWA ELECTRIC
TOEP C710656 10B YASKAWA Power Regenerative Unit - R1000 Instruction Manual
■
Installing the Regenerative Unit
1.
After wiring the main circuit, connect the terminal block to the regenerative unit as shown in
. Use the
installation screw to fasten the terminal block into place.
Figure 6.24
Figure 6.24 Install the Terminal Board
2.
Replace the terminal cover.
3.
Put the terminal cover back into its original place.
4.
When the power to the regenerative unit is first switched on, all parameter settings are transferred from the
terminal board into the regenerative unit memory. Should an oPE04 error occur, load the parameter settings that
have been saved on the terminal board onto the new regenerative unit by setting parameter A1-03 to 5550.
Reset timers used for the Maintenance Monitor function by setting parameters o4-01 through o4-12 back to 0,
and parameter o4-13 to 1.