6.4 Cooling Fans
YASKAWA ELECTRIC
TOEP C710656 10B YASKAWA Power Regenerative Unit - R1000 Instruction Manual
117
Pe
ri
odic
Ins
p
ec
tion &
Ma
inte
na
nce
6
3.
Install the replacement fan into the regenerative unit.
Figure 6.10
Figure 6.10 Install the Cooling Fan: 2A0035, 4A0035, 4A0043
4.
Tilt up the back end of the fan finger guard and slide the fan finger guard into the opening near the front of the
regenerative unit, then guide the fan finger guard into place.
Figure 6.11
Figure 6.11 Reattach the Fan Cover: 2A0035, 4A0035, 4A0043
5.
Press in on the hooks of the left and right sides of the fan cover and guide the fan finger guard until it clicks into
place.
Figure 6.12
Figure 6.12 Reattach the Fan Finger Guard: 2A0035, 4A0035, 4A0043
6.
Turn on the power supply and set o4-03 to 0 to reset the Maintenance Monitor cooling fan operation time.
Insert the fan at an angle so that it tilts
towards the front of the regenerative
unit. Next press down on the back of
the fan that still protrudes from the
regenerative unit so that the fan snaps
into place.
Insertion area
Front of
regenerative unit
Back of
regenerative unit
Fan finger guard
Back of regenerative unit
Front of unit
Hook
Hook
Cross-Section