Wiring
3.3.1 Wires and Suitable Crimp Connectors
3
-10
Table 3.4
400 V Class Inverter Power Cable Specifications
Wire Sizes
Model CIMR-
M5
Terminal Symbols
Terminal
Screw
Tighten-
ing
Torque
(N
S
m)
UL-approved
75
°
C (167
°
F)
Temperature-rated
Copper Wire
[AWG (mm
2
)]
600 V Vinyl-
sheath Insulated
Wire (IV, VV)
60
°
C (140
°
F)
(mm
2
)
600 V Cross-
linked Polyethy-
lene Wire (IC)
90
°
C (194
°
F)
(mm
2
)
600 V Rubber-in-
sulated Cabtyre
Cable (CT)
60
°
C (140
°
F)
(mm
2
)
P/
¨
, N/
©
M6
2.94
(*1)
45P5
U/T1, V/T2, W/T3
M5
2.35
12 (3.3)
2
2
2
M5
×
2
2.35
10 (5.3)
3.5
2
3.5
P/
¨
, N/
©
M6
2.94
(*1)
47P5
U/T1, V/T2, W/T3
M5
2.35
12 (3.3)
3.5
2
3.5
M5
×
2
2.35
10 (5.3)
3.5
2
3.5
P/
¨
, N/
©
M6
×
2
2.94
(*1)
4011
U/T1, V/T2, W/T3
M6
3.4 to 4.9
10 (5.3)
5.5
2
5.5
4011
M5
×
2,
2.1 to 2.5
10 (5 3)
3 5
2
3 5
M5
×
2,
M6
3.4 to 4.9
10 (5.3)
3.5
2
3.5
P/
¨
, N/
©
M6
×
2
2.94
(*1)
4015
U/T1, V/T2, W/T3
M6
3.4 to 4.9
8 (8.4)
8
3.5
8
4015
M5
×
2,
2.1 to 2.5
8 (8 4)
5 5
3 5
5 5
M5
×
2,
M6
3.4 to 4.9
8 (8.4)
5.5
3.5
5.5
P/
¨
, N/
©
M6
×
2
2.94
(*1)
4018
U/T1, V/T2, W/T3
M6
3.4 to 4.9
8 (8.4)
14
5.5
14
4018
M5
×
2,
2.1 to 2.5
8 (8 4)
8
5 5
5 5
M5
×
2,
M6
3.4 to 4.9
8 (8.4)
8
5.5
5.5
P/
¨
, N/
©
M6
×
2
2.94
(*1)
4022
U/T1, V/T2, W/T3
M6
3.4 to 4.9
6 (13.3)
14
8
14
4022
M5
×
2,
2.1 to 2.5
8 (8 4)
8
5 5
5 5
M5
×
2,
M6
3.4 to 4.9
8 (8.4)
8
5.5
5.5
P/
¨
, N/
©
M6
×
2
2.94
(*1)
4030
U/T1, V/T2, W/T3
M8
7.8 to 9.8
4 (21.2)
22
14
22
4030
M6
×
2,
3.4 to 4.9
6 (13 3)
14
8
8
M6
×
2,
M6
3.4 to 4.9
6 (13.3)
14
8
8
P/
¨
, N/
©
M6
×
2
2.94
(*1)
4037
U/T1, V/T2, W/T3
M8
7.8 to 9.8
3 (26.7)
30
14
30
4037
M6
×
2,
3.4 to 4.9
6 (13 3)
14
8
14
M6
×
2,
M6
3.4 to 4.9
6 (13.3)
14
8
14
P/
¨
, N/
©
M6
×
2
2.94
(*1)
4045
U/T1, V/T2, W/T3
M8
7.8 to 9.8
1 (42.4)
60
30
50
4045
M6
×
2,
3.4 to 4.9
6 (13 3)
14
8
14
M6
×
2,
M6
3.4 to 4.9
6 (13.3)
14
8
14
4011 to
4045
A12/r2, A22/t2 (*2)
M4
1.2 to 2.0
14 (2.1)
2
2
2
* 1. Connect using exclusive-use connection bus bar.
* 2. Provided for open chassis type with a minimum capacity of 11 kW. Not provided for external heatsink cooling type.
Notes: 1. Wire size is selected assuming external suspended wiring of single 3-core cables at
an ambient temperature of 30
°
C (86
°
F).
2. If ambient temperature exceeds 30
°
C (86
°
F), the allowable current of wire may be lowered.
3. Temperature for each wire indicates the maximum allowable conductor temperature.
3