No.
Name
Description
Range Def. Mode Addr.
Hex
Pg.
H3-13
Analog Input
Filter Time
Constant
Sets the primary delay filter time constant for
terminal A1 or potentiometer (optional). Used for
noise filtering.
0.00 to
2.00
0.03
s
O
41B
–
<1>
Parameter can be changed during run.
No.
Name
Description
Range Def. Mode Addr.
Hex
Pg.
H4: Multi-Function Analog Output AM
Use H4 parameters to configure the multi-function analog output terminal AM.
H4-01
Multi-
Function
Analog
Output
Terminal
AM
Selects the data to be output through multi-function
analog output terminal AM.
Set the desired monitor parameter to the digits
available in U
o
-
oo
. For example, enter “103” for
U1-03.
When using this terminal in through mode or when
not using it at all, set “000” or “031”.
000 to
999
102
O
41D
H4-02
Multi-
Function
Analog
Output
Terminal AM
Gain
Sets terminal AM output level when selected
monitor is at 100%.
Maximum output voltage is 10 V.
-999.9
to 999.9
100.0
%
S
41E
H4-03
Multi-
Function
Analog
Output
Terminal AM
Bias
Sets terminal AM output level when selected
monitor is at 0%.
-999.9
to 999.9 0.0%
O
41F
H5: MEMOBUS/Modbus Communications
Use H5 Parameters to connect the drive to a MEMOBUS/Modbus network.
The settings for MEMOBUS/Modbus communications become effective when the drive is restarted.
H5-01
Drive Slave
Address
Selects drive slave number (address) for
MEMOBUS/Modbus communication. Cycle power
for the setting to take effect.
0 to FF
1F
O
425
–
H5-02
Comm. Speed
Selection
Selects the baud rate for MEMOBUS/Modbus
communication. Cycle power for the setting to take
effect.
0 : 1200 bps
1 : 2400 bps
2 : 4800 bps
3 : 9600 bps
4 : 19200 bps
5 : 38400 bps
0 to 5
3
O
426
–
H5-03
Comm. Parity
Selection
Selects the communication parity for MEMOBUS/
Modbus communication. Cycle power for the setting
to take effect.
0: No parity
1: Even parity
2: Odd parity
0 to 2
0
O
427
–
B.2 Parameter Table
YASKAWA ELECTRIC TOEP C710606 25D YASKAWA AC Drive J1000 Installation & Start-Up Manual
235
B
Parameter List