u
E: Motor Parameters
E parameters set V/f characteristics and motor-related data.
No.
Name
Description
Range Def. Mode Addr.
Hex
Pg.
E1: V/f Pattern Characteristics
Use E1 parameters to set V/f characteristics for the motor.
E1-01
Input Voltage
Setting
This parameter must be set to the power supply
voltage.
WARNING! Drive input voltage (not motor voltage)
must be set in E1-01 for the protective features of the
drive to function properly. Failure to do so may result
in equipment damage and/or death or personal
injury.
155 to
255
200
S
300
E1-03
V/f Pattern
Selection
F: Custom V/f. E1-04 through E1-10 settings define
the V/f pattern.
F
F
O
302
—
E1-04
Maximum
Output
Frequency
E1-04, E1-06 to E1-10 can only be changed when
E1-03 is set to F.
To set linear V/f characteristics, set the same values
for E1-07 and E1-09. In this case, the setting for
E1-08 will be disregarded.
Ensure that the four frequencies are set according to
these rules to prevent triggering an oPE10 fault:
E1-09 ≤ E1-07 < E1-06 ≤ E1-04
E1-05
E1-08
E1-10
E1-09
E1-07 E1-06
E1-04
VACrms Out (V)
Frequency (Hz)
40.0 to
400.0
60
S
303
E1-05
Maximum
Output
Voltage
0.0 to
255.0
200
V
S
304
E1-06
Base
Frequency
0.0 to
E1-04
60
O
305
E1-07
Middle
Output
Frequency
0.0 to
E1-04
3.0
O
306
E1-08
Middle
Output
Frequency
Voltage
0.0 to
255.0
16.0
V
O
307
E1-09
Minimum
Output
Frequency
0.0 to
E1-04
1.5
S
308
E1-10
Minimum
Output
Frequency
Voltage
0.0 to
255.0
12.0
V
O
309
E2: Motor Parameters
Use E2 parameters to set motor-related data.
E2-01
Motor Rated
Current
Sets the motor nameplate full load current in
amperes.
Note:
Set E2-03 (Motor No-Load Current) before
making changes to E2-01. Setting E2-01 < E2-03 will
trigger an oPE02 error.
10 to
200% of
drive
rated
current
S
30E
B.2 Parameter Table
230
YASKAWA ELECTRIC TOEP C710606 25D YASKAWA AC Drive J1000 Installation & Start-Up Manual