No.
Parameter Name
Description
H4-01
Terminal AM Monitor
Selection
Select the data to output through multi-function analog output terminal AM.
Set the desired monitor parameter to the digits available in U
o
-
oo
. For
example, enter “103” for U1-03.
When using this terminal as a through terminal or when not using it at all, set
“000” or “031”.
Terminal AM Output Gain
Sets the voltage level gain of terminal AM. The bias to be added ranges from
0 to +/- 10% when 10 V is assumed to be 100%.
Terminal AM Bias Setting
Sets the voltage level bias for terminal AM.
The bias added is 0 to ±10% with a maximum voltage output of 10 V as 100%.
<1>
The parameter can be changed during run.
n
Changing Analog Output Settings
The following example illustrates how to program analog output terminal AM to generate a
signal proportional to drive output current (monitor U1-03).
Using H4-01 to Display Monitor Contents
Step
Display/Result
1.
Turn on the power to the drive. The initial display appears.
2.
Press
until the Parameter setting menu is displayed.
3.
Press
to enter the Parameter setting menu.
4.
Press
and
to select H4-01.
5.
Press
to display the value currently set to H4-01.
6.
Press
and
to set the output current (103).
7.
Save the setting by pressing
.
8.
The display automatically returns to the parameter setting menu.
9.
Press the
key until back at the Top Screen.
Adjusting the Analog Output Terminal Voltage with H4-02 and H4-03
Note:
This example continues from Step 3 in the previous example.
4.5 Basic Operation
112