Table 4.5 Drives with Heavy Duty Default Carrier Frequency of 10 kHz
200 V Single Phase Units
200 V Three Phase Units
Drive
Model
Rated Current [A]
Drive
Model
Rated Current [A]
2 kHz
10 kHz
15 kHz
2 kHz
10 kHz
15 kHz
BA0001
1.2
0.8
0.6
2A0001
1.2
0.8
0.6
BA0002
1.9
1.6
1.3
2A0002
1.9
1.6
1.3
BA0003
3.5
3.0
2.4
2A0004
3.5
3.0
2.4
BA0006
6.0
5.0
4.0
2A0006
6.0
5.0
4.0
Table 4.6 Drives with Heavy Duty Default Carrier Frequency of 8 kHz
200 V Single Phase Units
200 V Three Phase Units
400 V Three Phase Units
Drive
Model
Rated Current [A]
Drive
Model
Rated Current [A]
Drive
Model
Rated Current [A]
2 kHz
8 kHz 15 kHz
2 kHz
8 kHz 15 kHz
2 kHz
8 kHz 15 kHz
BA0010
9.6
8.0
6.4
2A0008
8.0
6.9
5.5
4A0001
1.2
1.2
0.7
—
—
—
—
2A0010
9.6
8.0
6.4
4A0002
2.1
1.8
1.1
—
—
—
—
2A0012
12.0
11.0
8.8
4A0004
4.1
3.4
2.0
—
—
—
—
2A0018
17.5
14.0
11.2
4A0005
5.4
4.8
2.9
—
—
—
—
2A0020
19.6
17.5
14.0
4A0007
6.9
5.5
3.3
—
—
—
—
—
—
—
—
4A0009
8.8
7.2
4.3
—
—
—
—
—
—
—
—
4A0011
11.1
9.2
5.5
u
Multi-Step Speed Operation (4-Step Speed)
Select up to 9 preset references (including Jog reference) using two multi-function inputs S4
and S5. Two multi-step references can be selected using two multi-function inputs as
illustrated in
n
Multi-Step Speed Operation Parameters
No.
Name
Description
d1-01 Frequency Reference 1
Frequency reference. o1-03 determines the units, with Hz as the default.
d1-02 Frequency Reference 2
Frequency reference when multi-function input “Multi-Step Speed Reference 1"
(H1-
oo
= 3) is on. Setting unit: set by o1-03.
d1-03 Frequency Reference 3
Frequency reference when multi-function input “Multi-Step Speed Reference 2”
(H1-
oo
= 4) is on. Setting unit: set by o1-03.
d1-04 Frequency Reference 4
Frequency reference when multi-function input “Multi-Step Speed Reference 1,
2" (H1-
oo
= 3 and 4) are both on. Setting unit: set by o1-03.
4.5 Basic Operation
YASKAWA ELECTRIC TOEP C710606 25D YASKAWA AC Drive J1000 Installation & Start-Up Manual
103
4
Start-Up Programming & Operation