2 - 1
RS-485 Connection
3
Chapter 2. WIRING
An example of connection methods in such a case is shown below.
• Connect terminating resistors of 150
Ω
±5%, 1/2W min. at each end of the trans-
mission line.
• Terminal block is required for the
CMQ-V
series because of the connector type
connection.
• The cable to the terminal block from the
CMQ-V
series must be as short as pos-
sible.
• The FG grounding must not be made at the both shielded wire ends but only at
one location.
• Yamatake’s
CMC10L001A000
can be used as a converter of the host station.
Handling Precautions
Be sure to connect SG terminals each other. Failure to do so might cause
unstable communications.
FG
FG
CMQ-V Series
(slave station)
CMQ-V Series
(slave station)
CMQ-V Series
(slave station)
CMQ-V Series
(slave station)
Terminating
resistor
Terminating
resistor
Shielded cable
Shielded cable
Terminal
block
Terminal
block
DA
DB
SG
DA
DB
SG
7
8
9
7
8
9
DA
DB
SG
FG
Master station
DA
DB
SG
DA
DB
SG
7
8
9
7
8
9
Содержание Azbil CMQ-V Series
Страница 43: ...35 Chapter 6 COMMUNICATION PROGRAM FOR MASTER STATION ...
Страница 44: ...36 Chapter 6 COMMUNICATION PROGRAM FOR MASTER STATION ...
Страница 45: ...37 Chapter 6 COMMUNICATION PROGRAM FOR MASTER STATION ...
Страница 46: ...38 Chapter 6 COMMUNICATION PROGRAM FOR MASTER STATION ...
Страница 52: ......
Страница 53: ...Revision History Printed Manual Number Edition Revised pages Description date Jan 2007 CP SP 1197E 1st Edition ...
Страница 54: ......
Страница 55: ......