Chapter 7.
TROUBLESHOOTING
■
Check items in case communication is disabled
(1) Check the power supply.
(2) Check the wiring.
(3) Check if the communication conditions for the
CMQ-V Series
meet those for
the host computer.
If any one of the following setting items is different between both stations,
communication is disabled:
The underlined items mean that they can be set on the
CMQ-V Series
side.
Transmission seed
: 38400, 19200, 9600, 4800, 2400bps
Data length
: 7, 8 bits
Parity
: No parity, odd parity, even parity
Stop bit
: 1 stop bit, 2 stop bits
(4) Check if the destination address of the command frame transmitted from the
host computer meets the address set to the
CMQ-V Series
.
The address of the
CMQ-V Series
set to “0” for factory setting.
Even when the destination address of the command frame is set to 00 (30H,
30H), the
CMQ-V Series
does not respond to such a message.
(5) Use the upper-case character codes for all the character codes other than the
device code (“X” or “x” in this controller).
(6) Are those multi-dropped controllers belong operated themselves with different
device address setups?
(7) Is the communication timing conformed with the
Chapter 4-5 Timing
Specifications
(page 16)?
39
Содержание Azbil CMQ-V Series
Страница 43: ...35 Chapter 6 COMMUNICATION PROGRAM FOR MASTER STATION ...
Страница 44: ...36 Chapter 6 COMMUNICATION PROGRAM FOR MASTER STATION ...
Страница 45: ...37 Chapter 6 COMMUNICATION PROGRAM FOR MASTER STATION ...
Страница 46: ...38 Chapter 6 COMMUNICATION PROGRAM FOR MASTER STATION ...
Страница 52: ......
Страница 53: ...Revision History Printed Manual Number Edition Revised pages Description date Jan 2007 CP SP 1197E 1st Edition ...
Страница 54: ......
Страница 55: ......