23
Chapter 5. COMMUNICATION DATA TABLE
■
Flow set value
Note
• For RD and WD commands, the data is required four hexadecimal digits.
• The flow rate unit "L/min" becomes "mL/min" in
MQV9200
.
■
Totalized flow related data
Note
• For RD and WD commands, the data is required four hexadecimal digits.
Item
Data range
RAM
EEPROM
Remarks
Address
R W
Address
R W
Decimal
Decimal
(Hexadecimal)
(Hexadecimal)
Flow set value SP-0
(0 to 100%FS)
1401
❍ ❍
4401
❍ ❍
L/min
(0579)
(1131)
Flow set value SP-1
(0 to 100%FS)
1402
❍ ❍
4402
❍ ❍
L/min
(057A)
(1132)
Flow set value SP-2
(0 to 100%FS)
1403
❍ ❍
4403
❍ ❍
L/min
(057B)
(1133)
Flow set value SP-3
(0 to 100%FS)
1404
❍ ❍
4404
❍ ❍
L/min
(057C)
(1134)
Flow set value SP-4
(0 to 100%FS)
1405
❍ ❍
4405
❍ ❍
L/min
(057D)
(1135)
Flow set value SP-5
(0 to 100%FS)
1406
❍ ❍
4406
❍ ❍
L/min
(057E)
(1136)
Flow set value SP-6
(0 to 100%FS)
1407
❍ ❍
4407
❍ ❍
L/min
(057F)
(1137)
Flow set value SP-7
(0 to 100%FS)
1408
❍ ❍
4408
❍ ❍
L/min
(0580)
(1138)
The value in the
data range (L/min)
is the value
removed decimal
point that obtained
by full scale flow
rate multiplied by
the percentage in
parentheses.
Item
Data range
RAM
EEPROM
Remarks
Address
R W
Address
R W
Decimal
Decimal
(Hexadecimal)
(Hexadecimal)
Totalized flow event
0 to 9999
1601
❍ ❍
4601
❍ ❍
setting lower 4 digits
(0641)
(11F9)
Totalized flow event
0 to 9999
1602
❍ ❍
4602
❍ ❍
setting upper 4 digits
(0642)
(11FA)
Totalized flow lower
0 to 9999
1603
❍ ❍
4603
❍ ❍
4 digits
(0643)
(11FB)
Totalized flow upper
0 to 9999
1604
❍ ❍
4604
❍ ❍
4 digits
(0644)
(11FC)
Same as RAM
address 2218 and
5218 in parameter
set up.
Same as RAM
address 2219 and
5219 in parameter
set up.
When resetting the
totalized value,
make sure to write
“0” for the both
lower and upper
digits.
Содержание Azbil CMQ-V Series
Страница 43: ...35 Chapter 6 COMMUNICATION PROGRAM FOR MASTER STATION ...
Страница 44: ...36 Chapter 6 COMMUNICATION PROGRAM FOR MASTER STATION ...
Страница 45: ...37 Chapter 6 COMMUNICATION PROGRAM FOR MASTER STATION ...
Страница 46: ...38 Chapter 6 COMMUNICATION PROGRAM FOR MASTER STATION ...
Страница 52: ......
Страница 53: ...Revision History Printed Manual Number Edition Revised pages Description date Jan 2007 CP SP 1197E 1st Edition ...
Страница 54: ......
Страница 55: ......