SEASONAL SERVICE

It is necessary to drain the entire system where the 

pump, tank, and piping will be subjected to freezing. 

Vertical pumps have a drain plug located on the side 

of the pump casing near the bottom of the pump. Ho-

rizontal pumps may have two drain plugs, one on the 

casing (part where pipes attach) and another on the 

motor adapter. They are also located near the bottom 

of the pump. Multi-stage pumps also have 1 or 2 drain 

plugs and they may require you to tip the pump or 

blow compressed air in one hole to get all the water 

out of the stages.

Power the Motor

The electrical supply must be a separate 

branch circuit with a properly sized breaker 

or fuses. All wiring must conform to National 

(NEC), CSA, state, provincial, and local codes. 

Power supply voltage, phase and controls must 

match motor.

NEVER RUN A PUMP DRY, DAMAGE WILL RESULT, 

AND THE WARRANTY WILL BE VOIDED!

ALWAYS DISCONNECT AND LOCK-OUT ALL 

ELECTRICAL POWER WHEN INSTALLING 

OR WORKING ON PUMPS, MOTORS, OR 

SWITCHES. INSURE THE POWER SUPPLY 

BREAKER IS OFF OR THE DISCONNECT 

(WHERE USED) IS OFF. 

Remove the pressure switch cover. Attach the power 

supply wires, either 115 or 230 depending on the mo-

tor voltage, to the Line terminals of the pressure switch. 

Attach the green or bare ground wire to either green 

ground screw in the switch. It makes no difference which 

Line terminal you attach the hot- L1 (usually Black) and 

neutral- N (usually white) 115 volt wires to on the switch. 

The same goes for a 230 volt hook-up, either wire can go 

on either Line terminal. Re-install the switch cover. 

NOTE:

 

Motor voltage is NOT changed in the pressure switch. 

See Fig. 7 in Technical Data

.

Check to insure that the motor is wired to match the 

incoming voltage. All motors have a sticker near the 

pressure switch that identifies the pre-wired voltage. All 

½

 

hp jet pumps are factory wired for 115 V, and ¾

 

hp 

and larger are wired for 230V. The motor voltage must 

be changed inside the motor cover, not in the pres-

sure switch. Make sure the breaker or disconnect is OFF 

before entering the motor cover. All motors have a wiring 

diagram on the cover label and it is also found in this 

manual. 

See Motor Wiring Diagram, Fig. 7, in Technical 

Data

.

BOOSTER SYSTEMS

Use the basic instructions for either a Shallow Well or Convertible with Shallow Well Adapter. If a city water booster 

system please plumb per Fig. 5

J, JS, JRS OR HSJ SERIES

 

If pumping from a cistern or water tank plumb    

 

per Fig. 6.

STORAGE TANK

GATE

VALVE

JET PUMP

HYDRO-

PRO

TANK

CHECK

VALVE

Fig. 6

Fig. 5

WATER MAIN

UNION

CHECK

VALVE

GATE

VALVE

GATE

VALVE

UNION

GAUGE

UNION

RELIEF

VALVE

Use flow control or ball valve 

 

on suction to throttle pump. Must 

be sized, or set, to load motor 

below maximum nameplate amps. 

Maximum inlet pressure should 

be limited so discharge does not 

exceed relief valve setting, or 100 

psi (0.68Pa) absolute maximum.

TO SIZE TANK 

PROPERLY –

MATCH 

DRAWDOWN 

OF TANK TO 

CAPACITY 

OF PUMP.

FUSE BOX

OR

SWITCH

MAIN POWER BOX

PRESSURE

SWITCH

BALL

VALVE

DANGER

Hazardous voltage

can shock, burn or

cause death.

DANGER

Hazardous voltage

can shock, burn or

cause death.

BOOSTER SYSTEMS

SEASONAL SERVICE

Содержание Goulds J Series

Страница 1: ...Jet Pumps INSTALLATION OPERATION AND TROUBLESHOOTING MANUAL INSTRUCTION MANUAL IM102R11...

Страница 2: ...ng orsystemtoapressurehigherthanthe tank smaximumpressurerating Thiswilldamage thetank voidsthewarrantyandmaycreateaserious hazard Protecttanksfromexcessivemoistureand sprayasitwillcausethetanktorusta...

Страница 3: ...e are two types of deep well jet assemblies twin pipe and packer systems Deep well pumps come in both vertical and horizontal designs and in single and multi stage models See Typical Installation Draw...

Страница 4: ...eck valve is to the well the easier the system will prime To prevent over pumping a low yield well you can throttle a jet pump using a ball valve in the suction line You should install a compound pres...

Страница 5: ...on Using smaller than recommended pipe may reduce gpm output The longer the pipe the worse the affect Install Packer Assembly To ease installation soak the 2 or 3 packer assembly in warm water to make...

Страница 6: ...AVC to replenish air lost through absorption The AVC requires connection to a vacuum port on the pump The suction side of the AVC must have a minimum 3 vacuum for 15 seconds when the pump starts Foll...

Страница 7: ...goes for a 230 volt hook up either wire can go on either Line terminal Re install the switch cover NOTE Motor voltage is NOT changed in the pressure switch See Fig 7 in Technical Data Check to insure...

Страница 8: ...P3 53 3 27 30 70 AV22 and JDW FT5B 48 4 40 70 110 FP3 54 3 30 70 110 FT4B 44 4 31 30 60 FP2 48 2 35 30 60 AWJ2 FT4B 43 4 33 60 80 FP2 43 2 36 60 100 AV22KIT J10 FT4B 18 4 35 80 110 AV22 and JDW FT5B 4...

Страница 9: ...DEPTH JET WELL CONTROL VALVE DEPTH PACKER CONTROL VALVE ASSEMBLY DIAMETER SETTING PSI TO JET ASSEMBLY DIAMETER SETTING PSI TO JET ADAPTER see fig 4 FT3 09 3 30 30 50 FP2 13 2 30 30 50 FT4B 13 4 30 30...

Страница 10: ...48C04A06 115 230 1 1 6 12 6 6 3 990 25 15 SFJ05860 JRS7 JRD7 JB07 C48C05A06 115 230 1 1 5 14 8 7 4 1200 30 15 SFJ06860 JRS10 JRD10 JB10 C48C06A06 1 115 230 1 1 4 16 2 8 1 1400 30 20 Effective July 199...

Страница 11: ...ess than pump capacity throttle a ball valve in suction line do not exceed 22 Hg to reduce pump capacity USE OF TAILPIPE ON DEEP WELL JET PUMPS If the capacity of a deep well jet pump exceeds the well...

Страница 12: ...method or means of repair or replacement Buyer s failure to comply with Seller s repair or replacement directions shall terminate Seller s obligations under this Warranty and render this Warranty voi...

Страница 13: ...Bombas de Inyecci n MANUAL DE INSTALACI N OPERACI N E IDENTIFICACI N Y RESOLUCI N DE PROBLEMAS MANUAL DE INSTRUCCI N IM102R11...

Страница 14: ...cedemasiadoeltanque las tuber asoelsistemaaunapresi nsuperiorala clasificaci ndepresi nm ximadeltanque Elhacerloda ar eltanque anulalagarant aypuedecrearunpeligrograve Protejaalostanquescontrahumedady...

Страница 15: ...profundos para elevaciones de m s de 25 pies y deben tener dos tuber as que vayan al pozo Hay dos tipos de conjuntos de inyecci n para pozos profundos los sistemas de tubo doble y los sistemas de obtu...

Страница 16: ...ra impedir bombear en exceso un pozo de baja producci n usted puede estrangular una bomba de inyecci n con una v l vula de bola en la l nea de succi n Usted debe instalar un indicador compuesto de pre...

Страница 17: ...n como los gpm disminuir n La bomba puede perder cebado f cil mente durante el bombeo debido a la restricci n Si se utiliza tuber a m s peque a que la recomendada podr a reducirse la salida de gpm Mie...

Страница 18: ...nstalan de la misma mane ra que los tanques precargados excepto que requieren un control de volumen de aire AVC para reponer el aire perdido por absorci n El control de volumen de aire requiere una co...

Страница 19: ...si n Co necte los alambres de la fuente de alimentaci n ya sea 115 230 dependiendo de la tensi n del motor a las terminales de l nea del interruptor por ca da de presi n Conecte el alambre verde o ala...

Страница 20: ...0 90 AV22KIT J7 FT4B 18 4 30 90 110 o FT5B 47 4 28 30 70 FP3 53 3 27 30 70 AV22 and JDW FT5B 48 4 40 70 110 FP3 54 3 30 70 110 FT4B 44 4 31 30 60 FP2 48 2 35 30 60 AWJ2 FT4B 43 4 33 60 80 FP2 43 2 36...

Страница 21: ...RADOR FT3 09 3 30 30 50 FP2 13 2 30 30 50 FT4B 13 4 30 30 50 AV15 JRD5 FT4B 31 4 30 30 70 FP2 31 2 30 30 60 AWJ2 o FT4B 08 4 30 60 90 FP2 08 2 30 60 80 AV22KIT FT5B 14 4 30 70 90 FT4B 14 4 27 30 60 FP...

Страница 22: ...B07 C48C05A06 115 230 1 1 5 14 8 7 4 1200 30 15 SFJ06860 JRS10 JRD10 JB10 C48C06A06 1 115 230 1 1 4 16 2 8 1 1400 30 20 Fecha de vigencia julio de 1998 230 V nicamente DATOS T CNICOS Fig 7 PROCEDIMIEN...

Страница 23: ...dad de la bomba estrangule una v lvula de bola en la l nea de succi n sin exceder 22 pulg de Hg para reducir la capacidad de la bomba USO DEL TUBO DE ASPIRACI N EN BOMBAS DE INYECCI N PARA POZOS PROFU...

Страница 24: ...o reemplazo ser a total discreci n del Vendedor Si el Comprador no cumple con las instrucciones de reparaci n o reemplazo del Vendedor esto rescindir las obligaciones del Vendedor conforme a la presen...

Страница 25: ...Pompes Jet MANUEL D INSTALLATION D UTILISATION ET DE D PANNAGE MANUEL D UTILISATION IM102R11...

Страница 26: ...meetler servoir nejamaisutiliser unepressionexc dantlapressionnominale maximaledecedernier afindenepasl endommager annulerla garantieniconstituerungravedanger Prot gerler servoirdes claboussuresetdes...

Страница 27: ...aux descendant dans le puits Il en existe deux types tuyaux jumel s ou tuyaux concentriques Les pompes pour puits profonds sont offertes en ver sions horizontales ou verticales multi tag es ou non Voi...

Страница 28: ...la cr pine ou dans la pompe Dans le cas des installations pointe filtrante ou en puits tubulaires on peut poser un clapet de non retour pr s de la t te de puits ou de la pompe et utiliser le cuvelage...

Страница 29: ...r le guide Ne pas poser de robinets de soupapes ni de filtres entre la pompe et le r servoir sauf s il s agit d un robinet vanne grand ouvert ou d un robinet tournant sph rique passage int gral La plu...

Страница 30: ...its profonds Amorcer un syst me pour puits profonds signifie remplir d eau les tuyaux d aspiration et d alimentation en eau motrice ainsi que la pompe Les pompes multi tag es ou non pour puits profond...

Страница 31: ...FONCTIONNER LA POMPE SEC CAR CELA L ENDOMMAGE RAIT ET ANNULERAIT LA GARANTIE ON DOIT TOUJOURS VERROUILLER LE DISJONCTEUR OU LE SECTIONNEUR SELON LE CAS DU CIRCUIT LEC TRIQUE EN POSITION OUVERTE HORS...

Страница 32: ...6 3 34 30 60 J15 FT5B 11 4 40 70 140 FP3 18 3 34 60 90 AV22KIT FP3 21 3 34 90 150 AV22 et JDW FP3 24 3 39 100 170 FT4B 48 4 37 30 70 FP2 51 30 70 SJ07 et FT4B 47 4 40 70 90 FP2 50 2 40 70 90 AWD2 HSJ0...

Страница 33: ...90 110 AV22 et JDW FT5B 47 4 27 30 70 S O FT5B 48 4 30 70 110 FT4B 44 4 31 30 60 FP2 48 2 35 30 60 FT4B 43 4 33 60 80 FP2 43 2 36 60 100 AWJ2 AV22KIT JRD10 FT4B 18 4 35 80 110 AV22 et JDW FT5B 49 4 28...

Страница 34: ...C48C04A06 115 230 1 1 6 12 6 6 3 990 25 15 SFJ05860 JRS7 JRD7 JB07 C48C05A06 115 230 1 1 5 14 8 7 4 1200 30 15 SFJ06860 JRS10 JRD10 JB10 C48C06A06 1 115 230 1 1 4 16 2 8 1 1400 30 20 230 V seulement p...

Страница 35: ...ire le d bit de celle ci l aide d un robinet tournant sph rique pos sur le tuyau d aspiration et r gl pour augmenter la d pression qui ne doit cependant pas d passer 22 po de Hg EMPLOI D UN TUYAU RALL...

Страница 36: ...de r paration ou de remplacement Le non respect de l Acheteur de se conformer aux directives de r paration ou de remplacement du Vendeur mettra fin aux obligations du Vendeur sous cette Garantie et a...

Отзывы: