Parameter name
Parameter number
Unit of measurement
Description
P51
Communication protocol -
Address [1-247]/[0-127]
This parameter sets the
desired address for the unit,
when connected to an
external device, depending
on the protocol selected in
P50:
• MOD: any value in the
1-247 range
• BAC: any value in the
0-127 range.
P52
Comm Protocol –
BAUDRATE [4.8, 9.6, 14.4,
19.2, 38.4, 56.0, 57.6
KBPS]
kbps
This parameter sets the
desired baud rate for the
communication port.
Default: 9.6 kbps.
P53
BACnet Device ID Offset
[0-999]
This parameter sets the
hundreds, tens and units of
the BACnet Device ID.
Default: 002.
Device ID default: 84002.
P54
Comm Protocol –
Configuration [8N1, 8N2,
8E1, 8o1]
This parameter sets the
length of the data bits, the
parity and the length of the
STOP bits.
6.6.6 Multi-pump configuration parameters
All these parameters affect MSE and MSY control modes.
Parameter number
Parameter name
Unit of measurement
Description
P55
Multipump – Address [1-3]
This parameter sets the
address of each pump
based on the following
criteria:
• Each pump needs an
individual pump
address (1-3)
• Each address may only
be used once.
Default: 1.
P56
Multipump – Max Units
[1-3]
G
This parameter sets the
maximum number of
pumps operating at the
same time.
Default: 3.
6 System Setup and Operation
Smart Pump Range INSTRUCTION MANUAL
39