Parameter number

Parameter name

Unit of measurement

Description

P03

Regulation Restart Value

[0-100]

G

%

It defines the start value

after the stop of the pump,

as a percentage of the P01

value. If the required value

is met and there is no

further consumption, then

the pump stops. The pump

starts again when the

pressure drops below P03.
P03 is valid when:

• Different from 100%

(100%=off)

• The control mode is

HCS, MSE or MSY.

Default: 100%.

P04

Auto-start [OFF-ON]

G

If P04 = ON, then the

pump starts automatically

following a power supply

disconnection.
If the pump is switched on

after setting P04 = OFF (see

Par. 6.5.1), it is stopped so

that the motor is not in

operation, and STP flashes

(STP 

 STP).

Default: ON.

P05

Operating time months

Total months of connection

to the electric mains, to add

to P06.

P06

Operating time hours

h

Total hours of connection to

the electric mains, to add to

P05.

P07

Motor Time Months

This parameter shows the

total operating time

months, to be added to

P08.

P08

Motor time hours

h

This parameter shows the

total operating time hours,

to be added to P07.

6  System Setup and Operation

Smart Pump Range INSTRUCTION MANUAL

31

Содержание GOULDS e-SVE Series

Страница 1: ...INSTRUCTION MANUAL IM326 Smart Pump Range Variable Speed Pump Unit...

Страница 2: ......

Страница 3: ...3 4 2 Pump specifications 11 3 5 Design and layout 12 4 Installation 14 4 1 Mechanical installation 14 4 1 1 Installation area 14 4 1 2 Unit installation 14 4 2 Hydraulic installation 15 4 3 Electric...

Страница 4: ...Sensor configuration parameters 36 6 6 5 RS485 Interface parameters 38 6 6 6 Multi pump configuration parameters 39 6 6 7 Test run configuration 41 6 6 8 Special parameters 41 7 Maintenance 43 7 1 Pre...

Страница 5: ...cation to the equipment or use of parts not provided by Xylem If there is a question regarding the intended use of the equipment please contact a Xylem representative before proceeding Do not change t...

Страница 6: ...afety equipment Use safety equipment according to the company regulations Use this safety equipment within the work area Hard hat Safety goggles preferably with side shields Protective shoes Protectiv...

Страница 7: ...e or remove any plugs while the system is pressurized Make sure that the pump is isolated from the system and that pressure is relieved before you disassemble the pump remove plugs or disconnect pipin...

Страница 8: ...ecycling Waste and emissions guidelines Do not dispose of equipment containing electrical components together with domestic waste Collect it separately in accordance with local and currently valid leg...

Страница 9: ...en the product by removing any screws bolts or straps Use care around nails and straps 4 If there is any issue then contact a sales representative 2 2 Unit handling WARNING Assembled units and their c...

Страница 10: ...m heat dirt and vibrations NOTICE Protect the product against humidity heat sources and mechanical damage NOTICE Do not place heavy weights on the packed product Ambient temperature Store this product...

Страница 11: ...put or the communication bus Controller constant pressure This mode is set as the default operating mode and is used for single pump operating units Cascade serial Cascade synchronous The units are co...

Страница 12: ...kW 9 Rated shaft power HP 10 Rated power speed range 3000 3600rpm 11 Rated efficiency 12 Insulation class 155 F LW155 1 13 NEMA KVA Code 14 Duty S1 Continuous 15 Max ambient temperature 16 Enclosure...

Страница 13: ...atalog number 2 Capacity Range 3 TDH Range 4 Rated Speed 5 Rated Horsepower 6 Maximum Operating Pressure 7 Maximum Fluid Temperature 8 Pump Serial Number 9 Rated Hz e SVE nameplate XYLEM INC 1 GOULDS...

Страница 14: ...Table 1 Description of components Position number Description Tightening torque 15 Nm in lbs 1 Screw 1 4 12 4 2 Terminal box cover 3 Optional module with strip 4 M12 I O cable gland 2 0 17 7 5 M20 ca...

Страница 15: ...onal components Table 2 Optional components Component Description Sensors The following sensors can be used with the unit Level sensor RS485 Module For the connection of a multi pump system to a super...

Страница 16: ...5 protection index is achieved make sure that the unit is closed correctly Before opening the terminal box cover make sure that there is no water in the unit Make sure that all unused cable glands and...

Страница 17: ...istance between units to ensure space for cabling 103 105 107 111 115 10 2 in 260 mm 303 305 307 311 315 322 11 8 in 300 mm 4 2 Hydraulic installation The following images show a single pump system an...

Страница 18: ...the system pressure and pre load it in accordance with the values indicated in the Quick Startup Guide code 001080128 4 3 Electrical installation Electrical Hazard The connection to the electric power...

Страница 19: ...the protection conductor ground is longer than the phase conductors in case of accidental disconnection of the power supply conductor the protection conductor ground must be the last one to detach it...

Страница 20: ...with electric components may cause death even after the unit has been switched off Before any interventions on the unit the network voltage and any other input voltages must be disconnected for the mi...

Страница 21: ...L2 1 2 3 10 A L1 1 L1 208 240 380 460 L2 L3 L1 L2 L3 4 3 2 1 3 RS001940 Figure 6 Wiring diagrams 4 Installation Smart Pump Range INSTRUCTION MANUAL 19...

Страница 22: ...4 3 2 1 1 3 RS001941 Figure 7 Connection label Table 7 1 I O terminals Item Terminals Ref Description Notes Fault Signal C 4 COM error status relay NO 5 NO error status relay Auxiliary Voltage Supply...

Страница 23: ...RS485 1P A GND 17 Electronic GND Communication bus B2 18 RS485 port 2 RS485 port 2 RS485 2N B active only with optional module RS 485 port2 for external communication A2 19 RS485 port 2 RS485 port 2...

Страница 24: ...d Lack of water detection enabled LoW 11 Low water reference Communication Bus B2 10 RS485 port 2 RS485 port 2 RS485 2N B active only with optional module RS 485 port2 for external communication A2 9...

Страница 25: ...put voltages must be disconnected for the minimum time indicated in Table 9 Table 9 Wait times Smart motor Minimum waiting time in minutes 4 5 Electrical Hazard Frequency converters contain DC link ca...

Страница 26: ...rol panel description RS001942 Figure 8 Control panel Position number Description Parameter 1 Decrease button 6 2 2 Increase button 6 2 3 START STOP and menu access button 6 2 4 POWER LED 6 3 1 5 Stat...

Страница 27: ...the parameter long press Main view see parameter 6 4 2 switches to parameter selection Parameters Menu switches to Main Visualization and Main view alternates between Speed and Head units of measure s...

Страница 28: ...he unit has not been addressed correctly for at least 5 seconds Condition 2 The communication bus protocol is the BACnet MS TP protocol the P50 parameter is set to the BACnet value No optional communi...

Страница 29: ...Note It has lower display priority than STOP mode STP STOP Pump stopped manually If the pump is switched on after setting P04 OFF see Par 6 5 1 it is stopped so that the motor is not in operation and...

Страница 30: ...a minimum value of 80 10xRPM after manual stop STP press ON once and after a few seconds 200 10xRPM With the pump in operation it is possible to display the Actual Head and the Actual Speed Example A...

Страница 31: ...n possibility Parameters Editing Visualization The value of a parameter may be changed using the buttons or the Modbus and BACnet communication protocols When returning to the Parameter Menu the displ...

Страница 32: ...every 3 seconds SOURCES SP SP internal required value Setpoint related to the control mode selected VL UL external required value speed Setpoint related to 0 10V input VALUE can represent a Speed or a...

Страница 33: ...hen the pump starts automatically following a power supply disconnection If the pump is switched on after setting P04 OFF see Par 6 5 1 it is stopped so that the motor is not in operation and STP flas...

Страница 34: ...logical occurred Other characteristics like P09 P11 3rd error Saves the third from the last error in chronological occurred Other characteristics like P09 P12 4th error Saves the fourth from the last...

Страница 35: ...the actual Control Mode ACT the motor starts and the value of P21 becomes the temporary ACT setpoint It can be changed by just entering a new value on P21 without confirming it otherwise it causes imm...

Страница 36: ...the difference between the pressure setpoint and the pressure feedback signal MSE Hydrovar Controller mode for multiple pumps in Serial Cascade Pumps are managed in series only the last activated pump...

Страница 37: ...amp used by the Hydrovar controller until the minimum speed of the pump is reached P27 It affects the control of the pump for HCS MSE and MSY control modes also see Par 6 6 2 Default 2 0 s P33 Ramp Sp...

Страница 38: ...or HCS MSE and MSY control modes also see Par 6 6 2 Default 80 P38 Speed Lift 0 MAX G rpmx10 This parameter sets the speed limit after which the linear increase of the actual require value starts P02...

Страница 39: ...auto calibration the 0 zero pressure is displayed or the message if the sensor signal is out of the permitted tolerance P45 Pressure Minimum Threshold 0 42 G bar psi Setting the minimum pressure thre...

Страница 40: ...the switch by displaying the corresponding alarm A06 on the display and keeping the motor running Err Err Err the unit reads the Lack Of Water Input enabled and reacts at the opening of the switch by...

Страница 41: ...nits of the BACnet Device ID Default 002 Device ID default 84002 P54 Comm Protocol Configuration 8N1 8N2 8E1 8o1 This parameter sets the length of the data bits the parity and the length of the STOP b...

Страница 42: ...35 bar P59 Multipump Actual Value Decrease 0 0 25 0BAR 0 0 363PSI G bar psi This parameter affects the calculation of P02 to improve the multi pump control as described in paragraph 6 6 3 Default 0 1...

Страница 43: ...from blocking Parameter number Parameter name Unit of measurement Description P65 Test Run Time Start 0 100 G h This parameter sets the time after which once the pump has stopped for the last time the...

Страница 44: ...frequency with which the unit stores the required value P02 in the EEPROM memory in order to extend its life This could be particularly useful in applications with BMS control devices that require con...

Страница 45: ...discharged by the built in discharge resistors 1 Make sure that the cooling fan and the vents are free from dust 2 Make sure that the ambient temperature is correct according to the limits of the unit...

Страница 46: ...y corrupted 1 Reset the default parameters using parameter P68 2 Wait 10 s 3 Restart the pump If the problem continues contact Xylem or the Authorised Distributor A06 LOW alarm Lack of water detection...

Страница 47: ...eck that there are no foreign bodies preventing the pump from turning Stop the pump for 5 minutes and then start it again If the problem continues contact Xylem or the Authorised Distributor E05 EEPRO...

Страница 48: ...e the tank E12 Pressure sensor error Missing pressure sensor not present in ACT mode Check the condition of the sensor connection cables E14 Low pressure error Pressure below minimum threshold not pre...

Страница 49: ...r supply mA Imax 40 Fault signal relay 1 x NO Vmax 250 VAC Imax 2 A 1 x NO Vmax 250 VAC Imax 2 A Motor status relay 1 x NO Vmax 250 VAC Imax 2 A EMC Electro Magnetic Compatibility See Par Declarations...

Страница 50: ...ting may occur at higher altitudes 9 2 Dimensions and weights B1 8 82 224 2 76 70 E1 3 15 80 4 61 117 8 82 224 2 91 74 6 10 155 E2 B5 5 87 149 B4 B5 2 68 68 0 91 23 B1 8 82 224 6 18 157 B4 10 91 277 4...

Страница 51: ...MHB 80 HM HB US 80 HM HB EU 16 76 7 6 202 3 9 2 29 10 13 2 32 19 14 6 35 49 16 1 10 55 268 3 54 90 3 15 80 3 94 100 4 92 125 ESM80 HMHC 80 HM HC US 80 HM HC EU 17 42 7 9 20 72 9 4 29 54 13 4 32 63 14...

Страница 52: ...and advanced analytics solutions for water electric and gas utilities In more than 150 countries we have strong long standing relationships with customers who know us for our powerful combination of...

Отзывы: