Parameter
Description
Power on
If after switching ON, parameter Menu View is accessed
with P23 = ON, P20 flashes: P20
→
P20.
Enter the password to display and change the
parameters.
Password timeout
If with P23 = ON no button is pressed for over 10
minutes from the last parameter Menu View, both the
view and the editing of the parameters are disabled.
Enter the password again to display and change the
parameters.
Parameters Menu
With P23 = OFF, or after entering the password (P20), it
is possible to both display and edit the parameters. When
accessing the Parameter Menu, the display shows:
P01
→
P01
P02
→
P02
...
P69
→
P69
The flashing parameter, indicating the selection
possibility.
Parameters Editing/Visualization
The value of a parameter may be changed using the
buttons, or the Modbus and BACnet communication
protocols.
When returning to the Parameter Menu, the displayed
parameter index is increased automatically. For further
information see Par. 6.5.
• Example A (P20) from 000 to 066:
P20
→
P20
→
→
000
→
000
→
… until …
→
066
→
066
→
sets the desired value
→
P21
→
P21
• Example 2 (P26) from 360 to 300:
P26
→
P26
→
→
360
→
360
→
… until…
→
300
→
300
→
sets the desired value
→
→
P26
→
P26.
6.5.3 Alarms and errors visualization
Parameter
Description
Alarm
In case of alarm, the corresponding code appears on the
display in alternation to the Main View.
For example:
A01
→
3.56 (ex. BAR)
A02
→
285 (ex. 10xRPM)
…
Error
In case of error, the corresponding identification code
appears on the display.
For example:
E01
E02
…
6 System Setup and Operation
Smart Pump Range INSTRUCTION MANUAL
29