Technical Reference
Application limits
Data
Description
Media (liquid)
temperature
Standard temperature version: Maximum temperature 40°C (104°F)
Standard version option, Warm media (liquid) version: Maximum temperature 70°C
(158°F)
Warm liquid has certain operational limitations, which are stated on a plate on the
pump.
pH of the pumped media
(liquid)
5–8
Media (liquid) density
Maximum density: 1100 kg/m
3
(9.2 lb. per US gal.)
Depth of immersion
20 m (65 ft.)
Other
For specific weight, current, voltage, power rating, and speed of the pump, see the data
plate on the pump. For starting current, see
For other applications, contact the local sales and service representative for information.
Motor data
Feature
Description
Motor type
Squirrel-cage induction motor
Frequency
50 or 60 Hz
Supply
3-phase
Starting method
• Direct on-line
• Internal soft starter
Maximum starts per hour 30 evenly spaced starts per hour
Code compliance
IEC 60034-1
Rated output variation
±10%
Voltage variation without
overheating
±10%, provided that it does not run continuously at full load
Voltage imbalance
tolerance
2%
Stator insulation class
H (180°C [360°F])
Specific motor data
3-phase, 50 Hz
Motor type:
• 2 pole
• 2,880 rpm
• 10 kW (13.4 hp)
Voltage, V
Rated current, A
Starting current, A
Power factor, cos
φ
220 D
34
195
0.91
230 D
33
205
0.88
240 D
34
215
0.83
380 D
20
124
0.88
Technical Reference
46
Flygt 2860.180 Installation, Operation, and Maintenance Manual
Содержание Flygt 2860.180
Страница 1: ...Installation Operation and Maintenance Manual Flygt 2860 180...
Страница 2: ......
Страница 41: ...4x WS001341A Maintenance Flygt 2860 180 Installation Operation and Maintenance Manual 39...
Страница 54: ......
Страница 55: ......