Xylem CentriPro Aquavar SOLO Скачать руководство пользователя страница 9

9

SWITCH INPUT - for connection of an external switch 

or control device used to start and stop the pump. Devices 

such as an over-pressure switch, level (float) switch or any 

other non-powered switch (time delay, flow, etc.) can be 

connected to this input. 
The Switch Input terminals have a Jumper Wire installed at 

the factory (do not confuse the jumper wire on the Switch 

Input with the Transducer Jumper next to the Transducer 

Connection Terminals, see Transducer Jumper below). 

The Switch Input terminals must be connected (closed) for 

the pump to operate. If they are not connected the Switch 

Input Status Light (visible inside the enclosure) will be Solid 

RED and the Controller Status Light will be Solid GREEN 

indicating that the pump-motor is off. Remove the Jumper 

Wire when connecting a float or over-pressure switch.

CONSTANT PRESSURE SYSTEM - with an Over-Pressure 

Switch: 

• Connect two wires from the Load and Lead connections 

of a pressure switch to provide over-pressure protection. 

In the event the pressure transducer fails, this will prevent 

high pressure from damaging piping.

• The over-pressure switch cut-out setting must be a mini-

mum of 10 PSI higher than the system set point pressure.  

• Set the over-pressure switch cut-out 5 - 10 PSI lower than 

the pressure relief valve (PRV) pop-off pressure.  This will 

turn the system off before the pressure relief valve opens. 

• Ex. On a system with a 50 PSI set point, set the over-pres-

sure switch cut-out at 60 PSI with a typical PRV setting of 

75 PSI.  In the event the transducer fails at high pressure 

the switch will turn the system off before the PRV pops.  

• Typical UIB Settings For This Type System:

• For 3AS controllers, 60 or 80 Hertz (depends on pump/

motor)

• For 1AS controllers, Pump Stop – High (switch to low if 

control cycles on/off)

• Dry Well - High (switch to low if it trips while pumping 

water)

• Low Pressure Cut-Off - On
• Pressure Drop - 5 PSI
• Transducer - Connected
• Transducer Jumper - Bottom Position (Factory Setting)
• Pressure Switch Connected to Switch Input

FLOAT SWITCH OPERATION - Filling a Pond or Tank 

(Non-Constant Pressure System): 

• Connect two wires from a float (level) switch to fill or 

empty a tank, pond, etc. The pump will run when the 

level switch contacts close. The maximum switch wire 

length tested is 200’. The pump will run at maximum 

speed when the float switch is closed.

• Typical UIB Settings For This Type System:

• 60 or 80 Hertz (depends on pump/motor)
• Pump Stop – High
• Dry Well - High (switch to low if it trips while pumping 

water)

• Low Pressure Cut-Off - Off
• Pressure Drop - 5 or 20 PSI
• Transducer - Not Connected
• Transducer Jumper - Top Position (Installer Must Move)
• Float Switch Connected to Switch Input

Checking for leaks

Constant pressure systems utilizing small tanks run 

whenever there is demand. Even small leaks can prevent 

a pump from turning off. To check for leaks, close all 

valves, turn power off to the controller, and note the 

pressure displayed on the pressure gauge. Tap the gauge 

to ensure you get an accurate reading.
Wait ten minutes and check the gauge again tapping to 

prevent the needle from sticking. If the pressure dropped 

then the system may have a leak*.
*If a system is pressurized after having been un-

pressurized, it will continue to expand for several 

minutes. This expansion causes the pressure to drop 

and can be misinterpreted as a leak. Allow a system to 

stabilize for 10 minutes under pressure before  

performing the aforementioned leak test.
A spring check valve placed on the pump side of the 

tank and transducer will often improve the ability of the 

system to shut down.

Checking Rotation – 3AS _ _ Models Only

This step only applies to controllers whose 

model no.’s begin with 3AS. Do not do this 

test with 1AS controllers. 
Single phase motors having Red, Black & Yellow wires 

must always be connected to the RED, BLK and YEL 

terminals only. Failure to do so will damage the motor.
For three phase motors, it is possible for the motor to 

rotate in the wrong direction. If running backwards, 

the pump will work but it will have greatly reduced 

performance.
To check rotation, perform the following tests: 

Connect an amp probe to one of the power supply 

wires. Run the system with several valves open and note 

the pressure and amps. Leave the valves open, turn the 

power off.

Electrocution Hazard. After turning off 

power, wait 5 minutes for hazardous 

voltages to discharge before proceeding to swap wires.
Swap red and black motor leads where they connect to 

the controller terminal block (NOT L1 and L2).
Turn power back on and let the system pressure 

stabilize. Again note the pressure and amps. Whichever 

wire position provided the most pressure/flow is the 

correct wire position. If there was little difference in the 

pressure/flow, then whichever had the lower amp reading 

is the correct wire position.
Turn the power off, wait 5 minutes and swap the wires 

back if necessary.
Replace the plastic protective covers on the terminal 

block.

4. SWITCH INPUT OPTIONS
Optional Switch Input and Switch Input  

Status Light

Electrocution Hazard. Opening SWITCH 

INPUT does not de-energize controller 

or any of its outputs. Always treat wire terminals of this 

controller as energized until power supply to the controller 

has been removed for 5 minutes.

DANGER

DANGER

4. SWITCH INPUT OPTIONS

WARNING

Содержание CentriPro Aquavar SOLO

Страница 1: ...AQUAVAR SOLO SUBMERSIBLE PUMP CONTROLLER INSTALLATION OPERATION AND TROUBLESHOOTING MANUAL INSTRUCTION MANUAL IM229R06...

Страница 2: ...tings Options 11 12 7 Troubleshooting Fault Codes 13 15 Limited Warranty 16 Table of Contents PLEASE USE THIS CONTROLLER INSTALLATION OPERATION AND TROUBLESHOOTING MANUAL IOM IN CONJUNCTION WITH THE P...

Страница 3: ...tisfactory performance and may void manufacturer s warranty WARNING WARNING WARNING WARNING 1 SAFETY INSTRUCTIONS WARNING NOTICE Some installations pull a vacuum on the transducer when the system is d...

Страница 4: ...ck valve between pump and tank for reliable turn off when flow stops TANK SIZING AND TANK PRESSURE SETTING Refer to Table 1 for recommended tank size On pre existing systems larger tanks may be used T...

Страница 5: ...ect The circuit board near the terminal block is labeled to show where to connect the motor wires For all motors the green wire from the motor must be attached to the terminal labeled GND For 2 wire 1...

Страница 6: ...to a Maximum of 50 C 122 F Ambient Temperature Output HP 14 12 10 8 6 4 3 2 1 1 0 2 0 3 0 4 0 250 300 350 400 500 690 1100 1748 2523 3978 6316 7884 9945 1 558 890 1413 2040 3216 5106 6375 8041 230V 1...

Страница 7: ...g value for pump motor Circuit Breaker or Dual Element Time Delay Fuse Size Amps protecting branch circuit supplying controller Minimum size of single phase 240 V genera tor required 230 Volt 200 Volt...

Страница 8: ...ng before applying power may damage the motor or wire and void the warranty Use Tables 3 and 4 to determine which controller and setting to use Note that some 200V motors require upsizing to the next...

Страница 9: ...0 PSI Transducer Not Connected Transducer Jumper Top Position Installer Must Move Float Switch Connected to Switch Input Checking for leaks Constant pressure systems utilizing small tanks run whenever...

Страница 10: ...tion resistance Condition of Motor and Leads Ohms Megohm Value Value A new motor without drop cable 20 000 000 20 0 or more A used motor which can be 10 000 000 10 0 reinstalled in the well or more Ne...

Страница 11: ...licable after a description there is a table showing which pushbutton s and DIP switch to use to make a particular setting The tables show which pushbutton s to hold down which DIP switch to flip and...

Страница 12: ...will also clear the restart time back to 1 minute Pushbutton DIP Switch Direction to Dry Well Restart Time to Hold to Flip Flip Down DIP Switch Increasing 1 10 20 30 60 min Both Top Left to Right Fix...

Страница 13: ...ler fault To clear the fault turn off power to the controller Red wait 1 minute turn on power to the controller If fault persists replace controller 2 Blinks Dry Well This fault can be caused by Water...

Страница 14: ...ation with megger Verify the error by turning power to controller off for 1 minute and then on Pump Motor must be checked if fault persists 5 Blinks Short Circuit This fault can be caused by Electrica...

Страница 15: ...nd replacements are available 8 Blinks Open Lead This fault can be caused by Disconnected or broken wire between the controller and motor Verify the error by turning power to controller off for 1 minu...

Страница 16: ...sement for loss caused by interruption of service c Reinstallation costs of replacement equipment For purposes of this warranty the following terms have these definitions 1 Distributor means any indiv...

Страница 17: ...AQUAVAR SOLO CONTROLADOR DE BOMBA SUMERGIBLE MANUAL DE INSTALACI N OPERACI N Y RESOLUCI N DE PROBLEMAS MANUAL DE LA INSTRUCCI N IM229R06...

Страница 18: ...ia de aislamiento y devanado 26 27 6 Ajustes Opciones avanzados 27 28 7 Resoluci n de problemas c digos de fallas 29 31 Garant a limitada 32 ndice Informaci n del propietario POR FAVOR USE ESTE MANUAL...

Страница 19: ...O FATALES O DA OS SIGNIFICATIVOSALAPROPIEDAD LEAYRESPETETODAS LAS INSTRUCCIONES DE SEGURIDAD EN ELMANUALYEN ELEQUIPO LAFINALIDAD DE ESTE MANUALESAYUDAR EN LA INSTALACI NYOPERACI N DE ESTAUNIDADYSE DE...

Страница 20: ...daciones Ubique el tanque y el transductor en donde no se puedan llegar a congelar Aseg rese de que la configuraci n de la presi n del sistema no exceda la presi n efectiva m xima del tanque Para un d...

Страница 21: ...C digo Nacional de Electricidad Art culo 250 El cable del transductor viene con un cable a tierra Verde y una abrazadera de conexi n a tierra para facilitar la tarea de conectar el transductor a tierr...

Страница 22: ...trolador motor 14 12 10 8 6 4 3 2 1 1 0 2 0 3 0 4 0 250 300 350 400 500 690 1100 1748 2523 3978 6316 7884 9945 1 558 890 1413 2040 3216 5106 6375 8041 1 445 709 1126 1625 2562 4068 5078 6406 8072 2 32...

Страница 23: ...dDeDetenci nDeBomba Frecuencia m xima Ca da de presi n Ca da de presi n Sensibilidad de Pozo Seco Sensibilidad de Pozo Seco Protecci n de Tuber a Rota Protecci n de Tuber a Rota ENCEN DIDO ENCEN DIDO...

Страница 24: ...n antes de que la bomba se reinicie se puede configurar en el est ndar de 5 PSI o en 20 PSI La configuraci n de 20 PSI provoca menos arranques en sistemas con p rdidas Se recomienda para sistemas de...

Страница 25: ...5 10 PSI por debajo de la presi n de salida de la v lvula de alivio de presi n PRV Esto apagar el sistema antes de que se abra la v lvula de alivio de presi n AJUSTE DE PRESI N SOLO SI SE DESEA UNA P...

Страница 26: ...tajo de la presi n baja Encendido cambie a apagado si la presi n cae 20 PSI o m s Ca da de presi n 5 PSI Transductor Conectado Puente de conexi n del transductor Posici n inferior configuraci n de f b...

Страница 27: ...os rojos cuando el pozo est seco primero aseg rese que el ajuste de sobrecarga del motor sea el correcto Luego realice la Calibraci n de energ a de pozo seco con el sistema en el flujo m ximo abra var...

Страница 28: ...Sensibilidad Alta utiliza 80 RESETEO MANUAL DE FALLA DE POZO SECO Al instalar y probar el sistema es conveniente tener una manera r pida de borrar una falla de Pozo Seco Si se presionan ambos botones...

Страница 29: ...a apague el espere 1 minuto vuelva a encenderlo Si la falla persiste reemplazar el controlador espere 1 minuto controlador vuelva a encenderlo Si la falla persiste reemplazar el controlador 2 Pozo sec...

Страница 30: ...nte con el megger Verifique el error apagando el suministro de energ a al controlador por 1 minuto y volvi ndolo a encender Si la falla persiste la bomba el motor deben ser revisados 5 Cortocircuito E...

Страница 31: ...rna del ventilador no est bloqueado o tapado Puede ser extra do para su limpieza y hay piezas de recambio disponibles 8 Conductor abierto Esta falla puede ser provocada por parpadeos Cable desconectad...

Страница 32: ...mplazo d Da os resultantes de cualquier tipo y e Reembolso de p rdidas causadas por la interrupci n del servicio A los fines de esta garant a los siguientes t rminos tienen estas definiciones 1 Distri...

Страница 33: ...AQUAVAR SOLO CONTR LEUR POUR POMPES SUBMERSIBLES MANUEL D INSTALLATION D UTILISATION ET DE D PANNAGE MANUEL D INSTRUCTION IM229R06...

Страница 34: ...e de contacteur fonctions 41 5 Essais de r sistance d isolement et de bobinage 42 6 R glages et choix volu s 42 7 D pannage et code des anomalies 45 Garantie limit e 48 Table des mati res UTILISER LE...

Страница 35: ...icant AVIS la vidange de certains syst mes peut causer une d pression dans le capteur Le nouveau contr leur prot ge celui ci contre les d pressions atteignant 57 56 kPa colonne de 17 po de mercure Le...

Страница 36: ...oir la table 1 pour les capacit s recommand es des r servoirs Des r servoirs plus gros sont permis dans les syst mes ant rieurs Table 1 Syst mes petits r servoirs D bit de la pompe Capacit totale mini...

Страница 37: ...fouissement ou l immersion ou les deux La figure 2 montre les bornes de connexion des fils d entr e et de moteur Les bornes de connexion du moteur sont indiqu es sur le circuit imprim voisin du bornie...

Страница 38: ...exposition une temp rature ambiante maximale de 50 C 122 F contr leur hp 14 12 10 8 6 4 3 2 1 0 00 000 0000 250 300 350 400 500 690 1100 1748 2523 3978 6316 7884 9945 1 558 890 1413 2040 3216 5106 637...

Страница 39: ...n activ e ON ou d sactiv e OFF 6 Chute de pression 5 ou 20 lbf po psi 7 R glage de la pression 8 Augmenter 9 R duire 10 S lecteur limiteur de surcharge du moteur 11 Voyant d tat 12 R glage de la surch...

Страница 40: ...gl e avant la mise sous tension peut ab mer le moteur ou le c blage et annuler la garantie Dans les tables 3 et 4 choisir le contr leur et l AFS appropri s Certains moteurs de 200 V requi rent le cont...

Страница 41: ...ENTR E DE CONTACTEUR connexion pour commande ou contacteur ext rieurs d marrant et arr tant le moteur ainsi que pour pressostat contacteur flotteur contacteur non aliment en courant etc pour le d bit...

Страница 42: ...ms est normale le bobinage du moteur n est pas la terre et l isolant du c ble n est pas ab m 2 Si la valeur en ohms est inf rieure la normale le bobinage est la terre ou bien l isolant du c ble est ab...

Страница 43: ...on n appuiera pas sur un bouton On peut modifier les r glages autant qu on le veut S assurer de replacer les commutateurs dans la position requise apr s le r glage R INITIALISATION DES R GLAGES PAR D...

Страница 44: ...RESSION DANS LA D TECTION D COULEMENT Le contr leur se sert de la variation de pression pour d tecter la fin de l coulement La variation par d faut est de 2 lbf po mais on peut choisir 1 lbf po et 3 l...

Страница 45: ...r leur Une anomalie s est produite dans le contr leur Pour effacer l anomalie couper le courant du contr leur attendre 1 min puis r tablir le courant Si l anomalie persiste remplacer le contr leur 2 c...

Страница 46: ...ompe et le moteur 5 cligno Anomalie Court circuit Cette anomalie peut tre caus e par tements une panne de moteur d origine lectrique la d faillance du c ble reliant le contr leur au moteur Couper le c...

Страница 47: ...il reliant le contr leur au moteur Couper le courant pendant 1 min puis le r tablir pour savoir si l anomalie persiste Si oui il faudra v rifier le moteur et le c blage le reliant au contr leur Couper...

Страница 48: ...ne couvre pas a les frais de main d uvre ni de transport ni les frais connexes encourus par le d taillant b les frais de r installation du mat riel r par c les frais de r installation du mat riel de r...

Отзывы: