The lengths in each of the Wire Sizing tables represent 100% of the allowable voltage drop when motor is running at full 

load. When sizing wire, the voltage drop of each wire segment must be included. The total must not exceed 100% of the 

allowable drop. Take for example a 1.5 HP 3Ø motor with a distance from Service Entrance to Controller of 100' and 500' 

between the Controller and Motor.
• Service Entrance to Controller  =  100' of 10 AWG (100/455)  =  22 %  (455' is from the S.E. to Controller chart)
• Controller to Motor 

=  500' of 12 AWG (500/709)  =  71 %  (709' is from the Controller to Motor chart)

 

Total Drop (must be 

 100%)   

93 %

If the distance from the Controller to Motor was 600' (600/709) = 85% + 22% = 107%, we would need to use #10 wire 

for that segment, ex. 600/1126 = 53% + 22% (for 100' of #10) = 75% which is acceptable. It is also acceptable to use dif-

ferent wire sizes for the Buried and Well sections of wire.

All Models – Service Entrance to Controller

 Controller Motor 

Copper Wire Size 75ºC Insulation Exposed to a Maximum of 50ºC (122ºF) Ambient Temperature 

  Input 

HP 14 12 10 8 6 4 3 2 1 1/0 

2/0 

3/0 

4/0 

250 

300 

350 

400 500

 

 

¾  279  445  706  1020 1608 2552 3186 4019 5065 6383 8055

 

 

1  226  360  571  824  1300 2064 2576 3250 4095 5161 6513 8201

 

230V  1½ * 

286

  455  657  1036 1644 2052 2589 3262 4111 5188 6533 8236 9710

 

1 PH  2 * * 

331

  478  754  1197 1495 1886 2376 2995 3779 4759 5999 7073  8455  9852

  

3  *  * 

246

  355  561  890  1111 1401 1766 2225 2808 3536 4458 5256  6283  7321  8343

  

5 * * * 

218

 

343

  545  680  858  1081 1363 1720 2165 2730 3219  3847  4483  5109  6348

3AS20, 30, 50 Controller to Motor – Controllers with 3Ø Motors

 Controller Motor 

Copper Wire Size 75ºC Insulation Exposed to a Maximum of 50ºC (122ºF) Ambient Temperature 

  Output 

HP 14 12 10 8 6 4 3 2 1 1/0 

2/0 

3/0 

4/0 

250 

300 

350 

400 500

 

 

¾  690  1100 1748 2523 3978 6316 7884 9945

 

 

1  558  890  1413 2040 3216 5106 6375 8041

 

230V 

1½  445  709  1126 1625 2562 4068 5078 6406 8072

 

3 PH 

2  324  516  820  1184 1866 2963 3699 4666 5879 7410 9351

 

 

3  241  384  609  880  1387 2202 2749 3467 4369 5506 6949 8750

 

 

*  235  373  539  849  1348 1683 2123 2675 3372 4255 5358 6755 7964  9520

  Reduce lengths by 13% for 200 V systems. 

*   Wire does not meet the N.E.C. ampacity requirement.

  Lengths in bold require 90º C wire. 

  Shading indicates 40º C maximum ambient.

Table 2: Wire Sizing

Maximum Cable Lengths in Feet to Limit Voltage Drop to 5% for 230 V Systems 

1AS15 Controller to Motor – Controllers with 2-Wire 1Ø Motors

Motor Lead Lengths - CentriPro 2-Wire Motors -  

Based on Service Factor Amps, 30º C Ambient and 5% Voltage Drop

 

Motor Rating 

60º C & 75º C Insulation - AWG Copper Wire Size

 

Volts 

HP kW SFA 14 12 10  8  6  4  2 1/0 2/0 3/0 4/0

  

½  0.37  4.7  466  742  1183 1874 2915 4648 7379 11733 14803 18688 23544

 

230

  ¾  0.55  6.4  342  545  869  1376 2141 3413 5419 8617 10871 13724 17290

 

 

1     

0.75 

9.1 

241 

383 

611 

968 

1506 

2400 

3811 

6060 

7646 

9652 

12160

   1½  1.1  11.0  199  317  505  801  1246 1986 3153 5013 6325 7985 10060

1AS15 Controller to Motor – Controllers with 3-Wire 1Ø Motors

Motor Lead Lengths - CentriPro 3-Wire Motors (CSIR) -  

Based on Service Factor Amps, 30º C Ambient and 5% Voltage Drop

 

Motor Rating 

60º C & 75º C Insulation - AWG Copper Wire Size

 

Volts 

HP kW SFA 14 12 10  8  6  4  2 1/0 2/0 3/0 4/0

  

½  0.37  6.3  348  553  883  1398 2175 3467 5505 8753 11044 13942 17564

  

¾  0.55  8.3  264  420  670  1061 1651 2632 4178 6644 8383 10582 13332

 

230 

1     

0.75 

9.7 

226 

359 

573 

908 

1413 

2252 

3575 

5685 

7173 

9055 

11408

   1½  1.1  11.1  197  314  501  793  1234 1968 3124 4968 6268 7913 9969
  

2  1.5  12.2  180  286  456  722  1123 1790 2843 4520 5703 7199 9070

Содержание CentriPro Aquavar SOLO

Страница 1: ...AQUAVAR SOLO SUBMERSIBLE PUMP CONTROLLER INSTALLATION OPERATION AND TROUBLESHOOTING MANUAL INSTRUCTION MANUAL IM229R06...

Страница 2: ...tings Options 11 12 7 Troubleshooting Fault Codes 13 15 Limited Warranty 16 Table of Contents PLEASE USE THIS CONTROLLER INSTALLATION OPERATION AND TROUBLESHOOTING MANUAL IOM IN CONJUNCTION WITH THE P...

Страница 3: ...tisfactory performance and may void manufacturer s warranty WARNING WARNING WARNING WARNING 1 SAFETY INSTRUCTIONS WARNING NOTICE Some installations pull a vacuum on the transducer when the system is d...

Страница 4: ...ck valve between pump and tank for reliable turn off when flow stops TANK SIZING AND TANK PRESSURE SETTING Refer to Table 1 for recommended tank size On pre existing systems larger tanks may be used T...

Страница 5: ...ect The circuit board near the terminal block is labeled to show where to connect the motor wires For all motors the green wire from the motor must be attached to the terminal labeled GND For 2 wire 1...

Страница 6: ...to a Maximum of 50 C 122 F Ambient Temperature Output HP 14 12 10 8 6 4 3 2 1 1 0 2 0 3 0 4 0 250 300 350 400 500 690 1100 1748 2523 3978 6316 7884 9945 1 558 890 1413 2040 3216 5106 6375 8041 230V 1...

Страница 7: ...g value for pump motor Circuit Breaker or Dual Element Time Delay Fuse Size Amps protecting branch circuit supplying controller Minimum size of single phase 240 V genera tor required 230 Volt 200 Volt...

Страница 8: ...ng before applying power may damage the motor or wire and void the warranty Use Tables 3 and 4 to determine which controller and setting to use Note that some 200V motors require upsizing to the next...

Страница 9: ...0 PSI Transducer Not Connected Transducer Jumper Top Position Installer Must Move Float Switch Connected to Switch Input Checking for leaks Constant pressure systems utilizing small tanks run whenever...

Страница 10: ...tion resistance Condition of Motor and Leads Ohms Megohm Value Value A new motor without drop cable 20 000 000 20 0 or more A used motor which can be 10 000 000 10 0 reinstalled in the well or more Ne...

Страница 11: ...licable after a description there is a table showing which pushbutton s and DIP switch to use to make a particular setting The tables show which pushbutton s to hold down which DIP switch to flip and...

Страница 12: ...will also clear the restart time back to 1 minute Pushbutton DIP Switch Direction to Dry Well Restart Time to Hold to Flip Flip Down DIP Switch Increasing 1 10 20 30 60 min Both Top Left to Right Fix...

Страница 13: ...ler fault To clear the fault turn off power to the controller Red wait 1 minute turn on power to the controller If fault persists replace controller 2 Blinks Dry Well This fault can be caused by Water...

Страница 14: ...ation with megger Verify the error by turning power to controller off for 1 minute and then on Pump Motor must be checked if fault persists 5 Blinks Short Circuit This fault can be caused by Electrica...

Страница 15: ...nd replacements are available 8 Blinks Open Lead This fault can be caused by Disconnected or broken wire between the controller and motor Verify the error by turning power to controller off for 1 minu...

Страница 16: ...sement for loss caused by interruption of service c Reinstallation costs of replacement equipment For purposes of this warranty the following terms have these definitions 1 Distributor means any indiv...

Страница 17: ...AQUAVAR SOLO CONTROLADOR DE BOMBA SUMERGIBLE MANUAL DE INSTALACI N OPERACI N Y RESOLUCI N DE PROBLEMAS MANUAL DE LA INSTRUCCI N IM229R06...

Страница 18: ...ia de aislamiento y devanado 26 27 6 Ajustes Opciones avanzados 27 28 7 Resoluci n de problemas c digos de fallas 29 31 Garant a limitada 32 ndice Informaci n del propietario POR FAVOR USE ESTE MANUAL...

Страница 19: ...O FATALES O DA OS SIGNIFICATIVOSALAPROPIEDAD LEAYRESPETETODAS LAS INSTRUCCIONES DE SEGURIDAD EN ELMANUALYEN ELEQUIPO LAFINALIDAD DE ESTE MANUALESAYUDAR EN LA INSTALACI NYOPERACI N DE ESTAUNIDADYSE DE...

Страница 20: ...daciones Ubique el tanque y el transductor en donde no se puedan llegar a congelar Aseg rese de que la configuraci n de la presi n del sistema no exceda la presi n efectiva m xima del tanque Para un d...

Страница 21: ...C digo Nacional de Electricidad Art culo 250 El cable del transductor viene con un cable a tierra Verde y una abrazadera de conexi n a tierra para facilitar la tarea de conectar el transductor a tierr...

Страница 22: ...trolador motor 14 12 10 8 6 4 3 2 1 1 0 2 0 3 0 4 0 250 300 350 400 500 690 1100 1748 2523 3978 6316 7884 9945 1 558 890 1413 2040 3216 5106 6375 8041 1 445 709 1126 1625 2562 4068 5078 6406 8072 2 32...

Страница 23: ...dDeDetenci nDeBomba Frecuencia m xima Ca da de presi n Ca da de presi n Sensibilidad de Pozo Seco Sensibilidad de Pozo Seco Protecci n de Tuber a Rota Protecci n de Tuber a Rota ENCEN DIDO ENCEN DIDO...

Страница 24: ...n antes de que la bomba se reinicie se puede configurar en el est ndar de 5 PSI o en 20 PSI La configuraci n de 20 PSI provoca menos arranques en sistemas con p rdidas Se recomienda para sistemas de...

Страница 25: ...5 10 PSI por debajo de la presi n de salida de la v lvula de alivio de presi n PRV Esto apagar el sistema antes de que se abra la v lvula de alivio de presi n AJUSTE DE PRESI N SOLO SI SE DESEA UNA P...

Страница 26: ...tajo de la presi n baja Encendido cambie a apagado si la presi n cae 20 PSI o m s Ca da de presi n 5 PSI Transductor Conectado Puente de conexi n del transductor Posici n inferior configuraci n de f b...

Страница 27: ...os rojos cuando el pozo est seco primero aseg rese que el ajuste de sobrecarga del motor sea el correcto Luego realice la Calibraci n de energ a de pozo seco con el sistema en el flujo m ximo abra var...

Страница 28: ...Sensibilidad Alta utiliza 80 RESETEO MANUAL DE FALLA DE POZO SECO Al instalar y probar el sistema es conveniente tener una manera r pida de borrar una falla de Pozo Seco Si se presionan ambos botones...

Страница 29: ...a apague el espere 1 minuto vuelva a encenderlo Si la falla persiste reemplazar el controlador espere 1 minuto controlador vuelva a encenderlo Si la falla persiste reemplazar el controlador 2 Pozo sec...

Страница 30: ...nte con el megger Verifique el error apagando el suministro de energ a al controlador por 1 minuto y volvi ndolo a encender Si la falla persiste la bomba el motor deben ser revisados 5 Cortocircuito E...

Страница 31: ...rna del ventilador no est bloqueado o tapado Puede ser extra do para su limpieza y hay piezas de recambio disponibles 8 Conductor abierto Esta falla puede ser provocada por parpadeos Cable desconectad...

Страница 32: ...mplazo d Da os resultantes de cualquier tipo y e Reembolso de p rdidas causadas por la interrupci n del servicio A los fines de esta garant a los siguientes t rminos tienen estas definiciones 1 Distri...

Страница 33: ...AQUAVAR SOLO CONTR LEUR POUR POMPES SUBMERSIBLES MANUEL D INSTALLATION D UTILISATION ET DE D PANNAGE MANUEL D INSTRUCTION IM229R06...

Страница 34: ...e de contacteur fonctions 41 5 Essais de r sistance d isolement et de bobinage 42 6 R glages et choix volu s 42 7 D pannage et code des anomalies 45 Garantie limit e 48 Table des mati res UTILISER LE...

Страница 35: ...icant AVIS la vidange de certains syst mes peut causer une d pression dans le capteur Le nouveau contr leur prot ge celui ci contre les d pressions atteignant 57 56 kPa colonne de 17 po de mercure Le...

Страница 36: ...oir la table 1 pour les capacit s recommand es des r servoirs Des r servoirs plus gros sont permis dans les syst mes ant rieurs Table 1 Syst mes petits r servoirs D bit de la pompe Capacit totale mini...

Страница 37: ...fouissement ou l immersion ou les deux La figure 2 montre les bornes de connexion des fils d entr e et de moteur Les bornes de connexion du moteur sont indiqu es sur le circuit imprim voisin du bornie...

Страница 38: ...exposition une temp rature ambiante maximale de 50 C 122 F contr leur hp 14 12 10 8 6 4 3 2 1 0 00 000 0000 250 300 350 400 500 690 1100 1748 2523 3978 6316 7884 9945 1 558 890 1413 2040 3216 5106 637...

Страница 39: ...n activ e ON ou d sactiv e OFF 6 Chute de pression 5 ou 20 lbf po psi 7 R glage de la pression 8 Augmenter 9 R duire 10 S lecteur limiteur de surcharge du moteur 11 Voyant d tat 12 R glage de la surch...

Страница 40: ...gl e avant la mise sous tension peut ab mer le moteur ou le c blage et annuler la garantie Dans les tables 3 et 4 choisir le contr leur et l AFS appropri s Certains moteurs de 200 V requi rent le cont...

Страница 41: ...ENTR E DE CONTACTEUR connexion pour commande ou contacteur ext rieurs d marrant et arr tant le moteur ainsi que pour pressostat contacteur flotteur contacteur non aliment en courant etc pour le d bit...

Страница 42: ...ms est normale le bobinage du moteur n est pas la terre et l isolant du c ble n est pas ab m 2 Si la valeur en ohms est inf rieure la normale le bobinage est la terre ou bien l isolant du c ble est ab...

Страница 43: ...on n appuiera pas sur un bouton On peut modifier les r glages autant qu on le veut S assurer de replacer les commutateurs dans la position requise apr s le r glage R INITIALISATION DES R GLAGES PAR D...

Страница 44: ...RESSION DANS LA D TECTION D COULEMENT Le contr leur se sert de la variation de pression pour d tecter la fin de l coulement La variation par d faut est de 2 lbf po mais on peut choisir 1 lbf po et 3 l...

Страница 45: ...r leur Une anomalie s est produite dans le contr leur Pour effacer l anomalie couper le courant du contr leur attendre 1 min puis r tablir le courant Si l anomalie persiste remplacer le contr leur 2 c...

Страница 46: ...ompe et le moteur 5 cligno Anomalie Court circuit Cette anomalie peut tre caus e par tements une panne de moteur d origine lectrique la d faillance du c ble reliant le contr leur au moteur Couper le c...

Страница 47: ...il reliant le contr leur au moteur Couper le courant pendant 1 min puis le r tablir pour savoir si l anomalie persiste Si oui il faudra v rifier le moteur et le c blage le reliant au contr leur Couper...

Страница 48: ...ne couvre pas a les frais de main d uvre ni de transport ni les frais connexes encourus par le d taillant b les frais de r installation du mat riel r par c les frais de r installation du mat riel de r...

Отзывы: