34
UNIT HEATER
SEDIMENT POCKET
SUPPLY LINE
AT LEAST 12" RETURN
CHECK VALVE
UNIT HEATER
VENT VALVE
UNIT HEATER
SEDIMENT POCKET
SUPPLY LINE
BUCKET TRAP
UNIT HEATER
VENT VALVE
STRAINER
UNIT HEATER
MINIMUM COOLING LEG 5'-0" LONG
TRAP
SUPPLY MAIN
GATE VALVE
GRAVITY VACUUM DRY RETURN MAIN
FULL SIZE
OF
TAPPING
SAME SIZE AS TRAP
UNIT HEATER
SEDIMENT
SUPPLY LINE
STRAINER
UNIT HEATER
MINIMUM COOLING LEG 5'-0" LONG
SAME SIZE AS TRAP
TRAP
TRAP
SUPPLY MAIN
GATE VALVE
GRAVITY VACUUM DRY RETURN MAIN
FULL SIZE
OF
TAPPING
Low pressure closed gravity system
High pressure system
Unit heater connections for two pipe gravity
or vacuum system
Unit heater connections for two pipe gravity or
vacuum system with supply branch dripped
through trap
Vacuum or low pressure open
gravity system
Piping connections for unit heaters (steam)
GRAVITY OR VACUUM DRY RETURN MAIN
GRAVITY OR VACUUM DRY RETURN MAIN