Installation and User Manual
ADPRO FastTx by Xtralis
106
Doc 11949_06
ADPRO FastTx monitors the internal temperature of the hard disk drives and has the option of
dialling the CMS and generating an alarm if the temperature exceeds an upper limit of 65°C.
If High Temperature Management is Enabled
When the internal temperature of the ADPRO FastTx rises above the high temperature
threshold, ADPRO FastTx will initiate an over-temperature condition and report this to ADPRO
VideoCentral. The ADPRO FastTx fault relay will activate during the over-temperature condition.
The ADPRO FastTx will continue to operate normally after reporting the over temperature
condition but urgent action must be taken to ensure that the ambient temperature complies with
ADPRO FastTx's 40°C maximum operating temperature specification. Continued operation at a
temperature exceeding the specified maximum may damage or reduce the useable life of
ADPRO FastTx.
When the temperature falls below the low temperature threshold, the over-temperature condition
will be cleared and the fault relay will deactivate.
If High Temperature Management is Disabled
No over-temperature alarm will be received by ADPRO VideoCentral and the fault relay will not
activate for an over-temperature condition.
Zone Isolate
The Zone Isolate feature allows a central monitoring station operator to prevent an alarm
detector from generating alarms. This feature is useful in a number of scenarios:
•
Commissioning a ADPRO FastTx
•
Fault finding an installation
•
Configuring detectors
•
Disabling faulty detectors
Any ADPRO VideoCentral operator is able to view the current state of detectors on the
connected ADPRO FastTx. However, only CMS operators can modify Zone Isolate status.
Observers are locked out from any Zone Isolate capability.
The isolation status of a zone will persist after a reboot of the ADPRO FastTx, allowing the
installer to rectify any detector problem before the detector is unisolated.
Zone Isolate Reminder
If zones are isolated on ADPRO FastTx, then a periodic reminder can be sent to ADPRO
VideoCentral from ADPRO FastTx highlighting an operator to this fact.
Figure 108: Zone Isolate Reminder Settings
This will remind the operator that zones have been isolated and that they should be unisolated.