THIS  APPLIANCE  CAN  BE  USED  BY  CHILDREN  AGED  FROM  8  YEARS 
AND  ABOVE  AND  PERSONS  WITH  REDUCED  PHYSICAL,  SENSORY 
CAPABILITIES  OR  LACK  OF  EXPERIENCE  AND  KNOWLEDGE  IF  THEY 
HAVE BEEN GIVEN SUPERVISION OR INSTRUCTION CONCERNING THE 
USE  OF  THE  APPLIANCE  IN  A  SAFE  WAY  AND  UNDERSTAND  THE 
HAZARDS  INVOLVED.  CHILDREN  SHALL  NOT  PLAY  WITH  THE 
APPLIANCE.

 

CLEANING  AND  MAINTENANCE  OF  THE  APPLIANCE  SHALL  NOT  BE 
MADE BY CHILDREN.

 

 

 

IMPORTANT 

 

1.

 READ ALL THESE INSTRUCTIONS & WARNINGS FULLY BEFORE COMMENCING INSTALLATION. 

2.

 INSTALLATIONS AND WIRING MUST CONFORM TO CURRENT IET REGULATIONS (UK), LOCAL OR APPROPRIATE REGULATIONS (OTHER COUNTRIES). IT IS THE 

INSTALLER’S RESPONSIBILITY TO ENSURE THAT THE APPROPRIATE BUILDING CODES OF PRACTICE ARE ADHERED TO.  

3.

 A QUALIFIED ELECTRICIAN MUST SUPERVISE ALL INSTALLATIONS. 

4.

 THESE APPLIANCES ARE INTENDED FOR CONNECTION TO FIXED WIRING. 

5.

 CHECK THAT THE ELECTRICAL RATING SHOWN ON THE FAN MATCHES THE MAINS SUPPLY. 

THE APPLIANCE IS DOUBLE INSULATED AND DOES NOT REQUIRE AN EARTH CONNECTION.

 

6.

 SITE  AWAY  FROM  DIRECT  SOURCES  OF  HEAT  (I.E.:  GAS  COOKERS  OR  EYE-LEVEL  GRILLS)  AND  NOT  WHERE  AMBIENT  TEMPERATURES  ARE  LIKELY  TO 

EXCEED 50°C. 

7.

 WHEN THE FAN IS INSTALLED IN A ROOM CONTAINING A FUEL BURNING APPLIANCE, THE INSTALLER MUST ENSURE THAT AIR REPLACEMENT IS ADEQUATE 

FOR BOTH THE FAN AND THE FUEL BURNING APPLIANCE. 

8.

 ENSURE  THAT  ALL  RELEVANT  SAFETY  PRECAUTIONS  (CORRECT  EYE  PROTECTION  AND  PROTECTIVE  CLOTHING  ETC)  ARE  TAKEN  WHEN  INSTALLING, 

OPERATING AND MAINTAINING THIS FAN. 

 

9.

 GENERAL GUIDANCE FOR SITING THE FAN SEE “FIG.H”. ALWAYS SITE FAN AS HIGH AS POSSIBLE.

 

10.

  IF ANY SECTION OF THE DUCTWORK IS POSITIONED HIGHER THAN THE FAN A CONDENSATION TRAP (XCT100) MUST BE FITTED AS CLOSE AS POSSIBLE TO 

THE FAN. 

 

 

 

For speed and ease of Installation, your installation 
may require some of the Ancillaries indicated in 
“Ancillary Options”

 

If installing in a wall (surface mounting) 

 

 

Mark on the wall the centre of the duct hole 

A

 

Use  this  centre  to  cut  an  opening  through  the  wall 
117mm diameter, with a slight fall to the exterior. 

3.

 

Fit the wall tube, not supplied, and mortar into place.

 

 

If installing in a wall (flush mounting) 

 

 

Mark on the wall the centre of the duct hole 

A

, and drill 

a pilot hole through both walls. 

 

Use the centre to mark a rectangular hole for the inner 
wall using the dimensions 

A

 

Cut the rectangular hole through the inner wall. 

 

Go  outside  and  cut  a  117mm  diameter  hole  in  the 
outer wall using the small hole as the centre. 

 

Measure the wall thickness. 

 

Cut  the  wall  tube  (WD100),  not  supplied,  so  that  it  is 
85mm less than the wall thickness.

 

 

If installing in a ceiling (surface mounting)  

 

This method requires a space above the ceiling, such as 
a  loft  or  attic,  to  provide  access  for  100mm  internal 
diameter  ducting,  or  a  minimum  70mm  void  using  flat 
ducting. 
 

 

Mark  on  the  ceiling  the  centre  of  the  duct  hole 

A

avoiding ceiling joists and buried cables etc. 

 

Cut a 117mm diameter hole using the marked centre.  

 
 

If installing in a ceiling (flush mounting)  
 

For 100mm diameter ducting: 
This method requires a space above the ceiling, such as 
a  loft  or  attic,  to  provide  access  for  100mm  internal 
diameter ducting. 

 

1. 

Mark a rectangular hole using the dimensions 

B

2. 

Cut the hole, avoiding ceiling joists and buried cables 

etc. 

 
For flat ducting: 

  This fan can be installed within a 140mm void with the 

circular spigot 

(Fig. 

F

).   

 

Preparing the fan for installation 

 

 

Remove the front cover 

(Fig. 

C

 

Fit  the  foam  tape 

12

  supplied  around  the  circular 

spigot

 7

 (Fig. 

E

). 

 

Remove the electrical cover 

(Fig. 

E

).  

 

Setting the condensation speed 

 

CF40DC / CF40TDDC / CF40RSTDDC

 Only (Fig. 

D

 

The  correct  condensation  control  speed  should  be 
selected to suit the room size in which the fan is to be 
installed.  Slide  the  switch 

X

  to  the  required  position. 

Please note that the fan is factory set to “Position 2”.  

 

 

Switch Position       Size / Room Volume (m

³

1                  Large (54 and above) 
2                  Medium (30 – 54) 
3                  Small (less than 30) 

 

Setting the trickle speed 

 

All models except 

DX400DC

 (Fig. 

D

 

The  fan  can  be  set  so  that  it  provides  constant  trickle 
extraction.  Slide  the  switch 

Y

  to  the  required  position. 

Please note that the fan is factory set to “Position 0”.  

Switch Position             Setting 

0                    Trickle extraction OFF 
I                     Trickle extraction ON 

 

Setting the Fan Speed (DX400DC Only) 

 

 

The fan can be set to High or Low Speed setting. Slide 
the switch 

Y

 to the required position. Please note that 

the fan is factory set to “Position 0”.

 

Switch Position             Setting 

0                      Low Speed 
I                       High Speed

 

 

Setting the time delay start 

 

DX400TDC / CF40TDDC

 Only (Fig. 

D

 

The fan can be set so that there is a 2-minute delayed 
start to its operation when used with an external on/off 
switch.  Slide  the  switch 

Z

  to  the  required  position. 

Please note that the fan is factory set to “Position 0”.  

 

Switch Position           Setting 

0                      Time delay start OFF 
I                       Time delay start ON 

 

Mounting the fan in a wall or ceiling (surface 
mounting)  

 

 

Place  the  ducting  into  the  hole  and  align  to  the 
required  position.  If  wall  mounting,  ensure  that  the 
ducting slopes down and away from the fan 

 

Mark  the  positions  of  the  three  fixing  holes 

A,

  in  Fan 

box 

6

 (Fig. 

E

).  

 

If  wall  mounting,  drill  three  holes  5.5mm  diameter  for 
wall  plugs  (supplied).  If  ceiling  mounting 

B

,  use 

appropriate fasteners (not supplied). 

 

Cut out the cable inlet hole, if required, in the surround 

10 

and  slit  the  cable  grommet.  Slide  the  surround 

10

 

over the fan box 

6

 

Pass  the  electrical  cables  into  the  fan  box 

6

  through 

the  rear  cable  inlet  hole  and  surround,  and  re-fit  the 
cable grommet. 

Ensure  that cable  grommet is in place  and  a  tight 
fit.  

 

 

Offer  the  fan  box 

6

  up  to  the  wall  or  ceiling.    Ensure 

the circular spigot 

7

 enters the ducting. 

 

Fix the  fan box 

6

 to the  wall using screws 

8

 or to the 

ceiling using appropriate fasteners (not supplied). 

 

If mounting in a wall (flush mounting) 
 

The  surround 

10

  is  not  required.  Fit  the  ducting  to  the 

circular spigot 

7

 

If the hole size is as recommended: 
 

 

Assemble the three fan body clamps 

9

 to the  fan  box 

6

 using screws 

8

 

Slit the cable grommet. Pass the electrical cables into 
the  fan  box 

6

  through  the  cable  inlet  hole  and  cable 

grommet.  

Ensure cable grommet is in place and a tight fit. 

 

Offer the fan box 

6

 up to the wall. Ensure the circular 

spigot 

7

 enters the ducting. 

 

Tighten up the three screws 

8

 until the fan is clamped 

to the inner  wall. The fan  body  clamps 

9

 will rotate to 

an automatic stop position. 

DO NOT OVERTIGHTEN

If  the  hole  size  is  larger  than  recommended  i.e.: 
larger  than  the  flange  on  the  fan  box 

6

  (Mostly 

relating to “retro-fit” installations): 
 

 

The fan body clamps ARE NOT suitable.  Construct a 
wooden  frame  of  INTERNAL  dimensions  232  x 
280mm.  Depth  should  be  at  least  50mm.  Fit  the 
wooden  frame  into  the  internal  wall  and  make  good 
the hole. 

 

Offer the fan box 

6

 up to the wall. Ensure the circular 

spigot 

7

 enters the ducting. 

 

Screw  the  fan  box 

6

  to  the  wooden  frame  using  the 

slots in the flange (screws not supplied). 

 

If mounting in a ceiling (flush mounting) 

 

 

The surround 

10

 is not required.  

 

Insert  the  fan  box 

6

  into  the  hole  and  mark  four 

positions using the slots in the flange 

B

 

Remove  the  fan  box 

6

  from  ceiling  and  fit  the  four 

ceiling  clips  (supplied)  over  the  edge  of  the  hole,  so 
that the clips align with the marks on the ceiling 

B

 

Drill  4  pilot  holes  into  the  ceiling  through  the  hole  of 
each clip, ensuring not to damage the clip, and fit the 
clips ensuring correct alignment. 

Содержание CF40DC

Страница 1: ...ull Cord CF40TDDC Pull Cord Timer CF40RSTDDC Remote Switched Timer Centrifugal Ducted Fans DX400DC Remote Switched DX400PCDC Pull Cord DX400TDC Remote Switched Timer Installation and maintenance instructions Retain for future reference GB F D NL a ...

Страница 2: ...C B A D ...

Страница 3: ...E ...

Страница 4: ...G F T A C H U H A C M IMP 1 R 2 I I 3 A 4 T 5 C TH 6 S E 7 W F 8 E O 9 G 10 TH Fo ma A If i 3 If i If i Th a dia duc M C If i Fo Th a dia 1 2 Fo T c Pr ...

Страница 5: ...40DC CF40TDDC CF40RSTDDC Only Fig D The correct condensation control speed should be selected to suit the room size in which the fan is to be installed Slide the switch X to the required position Please note that the fan is factory set to Position 2 Switch Position Size Room Volume m 1 Large 54 and above 2 Medium 30 54 3 Small less than 30 Setting the trickle speed All models except DX400DC Fig D ...

Страница 6: ... the on off switch When the switch is turned on the fan will operate at High Speed When the switch is turned off the fan continues to operate at low speed for the adjustable timer over run period light I is lit indicating fan is operating in manual mode An internal switch can be installer set to provide continuous background extraction in the Off state Time delay start feature on or off This is se...

Страница 7: ...FIJA 5 6 AVISO ESTOS EQUIPOS DEBEN ESTAR CONECTADOS A TIERRA 7 LEJOS DE FUENTES DIRECTAS DE CALOR P EJ COCINAS DE GAS O PARRILLAS Y NUNCA DONDE EXISTA LA POSIBILIDAD DE QUE LA TEMPERATURA AMBIENTE SEA SUPERIOR A LOS 50 C EL APARATO QUE QUEME COMBUSTIBLE POSIBLE 11 ES IMPORTANTE Pour que l installation soit plus rapide et plus facile il peut être nécessaire d utiliser les options auxiliaires indiqu...

Страница 8: ...0 ρησιµ π ιήστε κατσα ίδι ηλεκτρ λ γ υ και γυρίστε τη ίδα RH Σ D σύµ ωνα µε τη ρά τ υ ρ λ γι ύ για να αυ ήσετε τη ρύθµιση σ ετικής υγρασίας ή αντίθετα πρ ς τη ρά τ υ ρ λ γι ύ για να τη µειώσετε Σηµείωση ε αεριστήρας είναι πι ευαίσθητ ς σε σ ετική υγρασία 50 παρά 90 CF40TD CF40RSTD 1 Η περί δ ς παράτασης λειτ υργίας τ υ ρ ν ρυθµιστή µπ ρεί να ρυθµιστεί µετα ύ περίπ υ 30 δευτερ λέπτων και 20 λεπτών ...

Страница 9: ...tte des Kanalloches A markieren und ein kleines Loch durch beide Wände bohren 2 Mit Hilfe dieses Mittelpunktes und unter Verwendung der Abmessungen A ein rechteckiges Loch für die Innenwand markieren 3 Das rechteckige Loch durch die Innenwand schneiden 4 Nach draußen gehen und ein Loch mit 117 mm Durchmesser in die Außenwand schneiden Dabei das kleine Loch als Mittelpunkt benutzen 5 Die Wandstärke...

Страница 10: ...Uhrzeigersinn und zur Verkürzung im Gegenuhrzeigersinn drehen Die Nachlaufzeit ist werksseitig auf circa 10 Minuten 1 Das Niveau der Feuchtigkeitseinstellung kann zwischen 50 und 90 relative Luftfeuchtigkeit reguliert werden Mit einem Elektroschraubenzieher die Schraube RH Abb zur Erhöhung der Feuchtigkeitseinstellung im Uhrzeigersinn und zur Reduzierung im Gegenuhrzeigersinn drehen Hinweis der Ve...

Страница 11: ... Η µέθ δ ς αυτή απαιτεί ώρ πάνω απ τ τα άνι πως για παράδειγµα πατάρι ή σ ίτα π υ να παρέ ει πρ σ αση για αγωγ εσωτερικής διαµέτρ υ 100 λστ ή ελά ιστ κεν 70 λστ ρησιµ π ιώντας επίπεδ αγωγ 1 Σηµαδέψτε ρθ γώνια τρύπα ρησιµ π ιώντας τις διαστάσεις B 2 Κ ψτε την τρύπα απ εύγ ντας τα πατ υλα τ υ τα ανι ύ τα καλυµµένα καλώδια κλπ Για επίπεδ αγωγ ε αειρστήρας αυτ ς µπ ρεί να εγκατασταθεί µέσα σε κεν 140 ...

Страница 12: ...smiddelen 4 Laat de ventilator grondig drogen voor u hem gebruikt 5 Behalve schoonmaken is geen ander onderhoud vereist Legende E 1 Afdekplaat 2 Schermplaat 3 Schoep 4 Bevestigingsschroeven 5 Aansluitafdekking 6 Ventilatorhuis 7 Ronde luchtinlaat 8 Klemschroeven en muurpluggen 3 stuks 9 Ventilatorklemmen 3 stuks 10 Montageplaat 11 Plafondschroeven 25 mm lang 4 stuks schema B 12 Schuimband Koppla i...

Страница 13: ...ا I د ل رو ا ر ء ا I 1 ور و ا د ا 2 را ح إ راف ا ر رك ھذه رة ا رو ا د ر دم ا رات دة ا م ب ر ا ر و و د ج ض ت ا واردة ا ه أد WD100 وب أ دار ا CFWG100 دار ا ز ا XCT100 دة ف ب ا اء ا ال ا DGW B SP100 اء ا ب ا ل XAA ة ر VC10 ري ء ا WT10 ن ري 230 x 25 ا 29 234 XF FM ...

Страница 14: ...1 B H9 1D5 I 9 ED5C 85 8E 949DI C5DD9 7 9C 14 ECD12 5 25DG55 1 B H9 1D5 I 1 4 B5 1D9F5 8E 949DI C5 1 5 53DB9391 jC C3B5G4B9F5B 1 4 DEB C3B5G g h 97 D 3 3 G9C5 D 9 3B51C5 D85 B5 1D9F5 8E 949DI C5DD9 7 1 4 1 D9 3 3 G9C5 D 453B51C5 D5 D85 61 9C B5 C5 C9D9F5 1D D81 1D 85 D9 5B F5B BE 5B9 4 31 25 14 ECD54 25DG55 1 B H9 1D5 I C53 4C 1 4 9 ED5C C5 1 5 53DB9391 jC C3B5G4B9F5B 1 4 DEB C3B5G g h 97 D 3 3 G9...

Страница 15: ...NALES OU AUX AUTRES REGLEMENTATIONS APPROPRIEES AUTRES PAYS IL APPARTIENT A L INSTALLATEUR DE RESPECTER LES CODES APPROPRIES DE PRATIQUE DU BATIMENT 3 UN ELECTRICIEN QUALIFIE DOIT SUPERVISER TOUTE L INSTALLATION 4 CES APPAREILS SONT DESTINES A ETRE RACCORDES A DES CABLES FIXES 5 VERIFIEZ QUE LES SPECIFICATIONS ELECTRIQUES INDIQUEES SUR LE VENTILATEUR CORRESPONDENT A CELLES DE L ALIMENTATION SECTEU...

Страница 16: ...elair com Technical Advice Service UK Xpelair have a comprehensive range of services including Free technical advice Help Desk from Engineers on all aspects of ventilation Free design service quotations and site surveys Outside UK See International section below Please ask for details on Tel 44 0 844 372 7766 Fax 44 0 844 372 7767 Email service request redringxpelair com Also at the address below ...

Отзывы: