Flag register
The flag can control the remote equipment stop, detect the signal and so on. this function
must be configured through USB port in XNET mode.
4GBOX connection
4GBOX will communicate with PLC, set ON the appointed address every 5s after module
initialization.
Signal strength
4GBOX will communicate with PLC, write the signal strength in appointed address every
5s after module initialization. The signal range is 0 to 31, 31 is the strongest.
SIM card change
After the module initialization, 4GBOX will communicate with PLC, set ON the appointed
address every 5s, if SIM is binding, reset the address every 5s.
Note:
(1)
4GBOX connection, SIM card change appointed address type: Y, M, HM, S, HS, T,
HT, C, HC.
(2)
Signal strength appointed address type: D, HD, TD, HTD, CD, HCD, FD.
User authority
It is white list function. If the list is no phone number, 4GBOX will execute the message
control instruction without distinguishing the phone number. if there is phone number in the
list, 4GBOX will distinguish the number and authority to monitor the equipment.
Message function
Message monitoring(phone => 4GBOX => PLC)
User can edit the message as fixed format to monitor the equipment.
Read soft component (example)
Sending message format: R M0 returning message format: M0=ON
Sending message format: R D5 returning message format: D5=K1234
Sending message format: R DD0 returning message format: DD0=K654321
R D0 S20 return Thinget Made (S means the string length in decimal format expected to be
read)
Write soft component
Sending message format: W M0 1 //set ON M0
Sending message format: W Y23 0 //set OFF Y23
Sending message format: W Y35 1 //set ON Y35
Sending message format: W D5 K1234 //D5=1234(decimal format)
Sending message format: W DD0 H654321 //DD0(double word)=654321(hex
format), DD0 occupies D0 and D1.
W D0 “XINJE Made” //write the string in the address starting from D0 (occupy
D0…….Dn, total n characters)
Error code:
If the message format, user authority, soft component type is error, the returning message
will be error code. If there is no error, the returning message is OK.
Error1: the phone number which sending the message is not in the white list.
Error2: message format is not correct
Error3: the soft component is not correct
Error4: the phone number only has read authority, but it wanted to write in
Error5: 4GBOX and PLC BWO read write failure
Error6: 4GBOX and PLC BWO read write failure
Error7: 4GBOX and PLC BWO read write failure
Error8: 4GBOX and PLC BWO read write failure
Note:
(1)
all the letters must be capitalized.
(2)
The command, register, operands are separated by a space, the whole message
should not exceed 99 English characters.
(3)
To send the character message, quotation mark must be English half angle “
(4)
Message function only support China mobile, China unicom.
Message sending (PLC => 4G-BOX => phone)
The 4GBOX will send message to user’s phone in certain condition. Please refer to below
example.
The trigger coil should be edge signal(falling or rising edge of pulse).
In the message configuration window, 4GBOX connects the left extension
port of XD series PLC, set the port to com3
First address can be D or HD, these registers cannot be used in other place of
program
Support multi phone number type-in and set the phone number on the HMI,
the using method please refer to above picture, multi numbers are separated
by “,”
The message support Chinse and English contents, such as “present temp
{HD0}”, and user will receive the message “present temp 30” for example.
Register analysis function supports single and double words, such as D, DD,
HD, DHD, but not support DM.
China mobile, China unicom SIM card support Chinese/English and register
analysis function, China telecom only supports English and register analysis
function.
Online monitoring
Serial port setting
1.
Connect XD series PLC with PC through USB cable, open the XINJE config tool,
click config/find device/Xnet find.
2. choose PLC for device type, click confirm.
3. after finding the device, click config/single device/com port
4. choose comportNo 3, click ReadConfig. The Net please choose X-Net. PHY please
choose TTL. The NetType please choose PPFD. The baud rate please set to 1000000.
NetID and StationID no need to change. Then click WriteConfig, it will show “write
configuration success”.