This series inverter records the codes of latest 6 fault and operating parameters of last 1 fault which can be help for finding
the possible reason of faults. All of these fault informations are saved in group P6. Please refer operation methord of
keyboard to enter group P6.
5-3.
5-3.
5-3.
5-3. Fault
Fault
Fault
Fault reset
reset
reset
reset
Once the fault occurs, select one of the following operations to restart the inverter:
(1) When fault code displayed in the operation panel, press
key after you confirm the inverter can be reset.
(2) After setting one terminal among X1
~
X8 as external RESET input (P4.00
~
P4.07=17), connect it with COM terminal
and then disconnect them.
(3) Cut off the power supply
(1) Please make sure you know the reason of the fault and get rid of it before resetting, otherwise the inverter may be
damaged permanently.
(2) If the inverter can not be reset or fault reoccurred after resetting , please check the reason as the inverter may be
damaged by resetting continuously.
(3) Delay 5 minutes to reset when overload and overheat protection are enabled.
E-17
E
2
PROM
W/R error
W/R error of control parameter
Press
key to reset or seek service
E-18
DC brake overcurrent Set wrong current of DC brake
Decrease the brake current %
E-24
Main circuit lack
voltage,the
electromagnetic
contacter action error
Lack of phase when input current, momentary
power off, power supply point loose, power
supply voltage fluctuates serious and make the
main circuit contacter open
Check the reason and reset
Check the power supply
Ask the factory
E-30/31
Lack of phase when
inverter running or
stop
Input power supply lack of phase, momentary
power off, power supply point loose, power
supply voltage fluctuates serious and make the
voltage between phases unbalance
Check the reason then reset
EEEE
Panel communication
error
Operate panel and CPU board connection is not
good, the control circuit of inverter is not good
Uninstall the operate panel and install again, ask
the factory for help