3.0 Parameter Instructions
1 2 3
5 6 7
8
4
Parameter Instructions
No.
Code
Function
Setting Range
Default
1
TS
Temperature
Set-point
-40 - 110
25
-40 - 230
77
2
CD
Cooling
Differential
0.2 - 15
2.0
1 - 30
3
3
HD
Heating
Differential
0.2 - 15
2.0
1 - 30
3
4
PT
Protection Time
0 - 10
3
5
AH
High Alarm Limit
-40 - 110
35
-40 - 230
95
6
AL
Low Alarm Limit
-40 - 110
0
-40 - 230
32
7
CA
Temperature Calibration
-10 - 10
0
-1 5 - 1 5
0
8
CF
3
Temperature Unit
°C/°F
°C
°F
°C
°F
°C
°F
°C
°F
°C
°F
°C
°F
C
Unit
min
---
Note:
3
The°C/°F icon will flash on the LCD during temperature unit settings.