Installation
Load Connections
42
Operating Manual for XPR Series Power Supply
Single Load
To connect a single load to the DC output bus bars (5–80V outputs):
1. Ensure that the power supply is powered OFF.
2. Place a 5/16 in. (M8) bolt in the connecting hole of the negative bus bar, and
fasten the negative wire or bus bar, a flatwasher, lockwasher, and a nut to the
bolt.
3. Using a wrench, turn the bolt until it is secure at approximately 25 foot-pounds
(34Nm).
4. Fasten the positive wire or bus bar to the positive bus, using a bolt, flatwasher,
lockwasher, and nut.
5. Tighten the bolt to approximately 25 foot-pounds (34Nm).
6. Ensure that the positive and negative wires are arranged so bare wires do not
come into contact with each other or the chassis.
To connect the DC output wire clamp connectors (100–600V outputs):
•
Connect appropriately sized wires as described in steps 1 to 6 above, except strip
0.5 in. (13 mm) of insulation off each load wire, and clamp in the output
connector by securely tightening the vertical clamp screw for each output.
Содержание XPR 10-600
Страница 2: ......
Страница 3: ...Operating Manual for XPR 6000 Watt Series Programmable DC Power Supply...
Страница 10: ...About This Manual viii Operating Manual for XPR Series Power Supply...
Страница 14: ...Contents xii Operating Manual for XPR Series Power Supply...
Страница 16: ...List of Tables xiv Operating Manual for XPR Series Power Supply...
Страница 18: ...List of Figures xvi Operating Manual for XPR Series Power Supply...
Страница 26: ...About The XPR Power Supply Rear Panel Connectors and Switch 24 Operating Manual for XPR Series Power Supply...
Страница 48: ...Installation Remote Sensing 46 Operating Manual for XPR Series Power Supply...
Страница 60: ...Operation Alarms 58 Operating Manual for XPR Series Power Supply...
Страница 79: ......