Installation
Load Wiring
40
Operating Manual for XPR Series Power Supply
Load Wiring
Length for
Operation
with Sense
Lines
For applications using remote sensing, or for improved voltage regulation at the load,
you must limit the voltage drop across each load line. We recommend that you use
larger load wiring to ensure a smaller voltage drop (1V maximum under full load
conditions), although units will compensate for up to 5V drop in each line with the
remote sense lines connected. The combined voltage drop across the load lines and
load cannot exceed the rated output of the supply.
Noise and
Impedance
Effects
To minimize noise pickup or radiation, use the shortest possible length of
shielded-twisted pair wiring for load lines. Connect the shield to the chassis via a rear
panel mounting screw. Where shielding is not possible or is impractical, twisting the
wires together offers some noise immunity. When using local sense connections, use
the largest practical wire size to minimize the effects of load line impedance on the
regulation of the supply.
Содержание XPR 10-600
Страница 2: ......
Страница 3: ...Operating Manual for XPR 6000 Watt Series Programmable DC Power Supply...
Страница 10: ...About This Manual viii Operating Manual for XPR Series Power Supply...
Страница 14: ...Contents xii Operating Manual for XPR Series Power Supply...
Страница 16: ...List of Tables xiv Operating Manual for XPR Series Power Supply...
Страница 18: ...List of Figures xvi Operating Manual for XPR Series Power Supply...
Страница 26: ...About The XPR Power Supply Rear Panel Connectors and Switch 24 Operating Manual for XPR Series Power Supply...
Страница 48: ...Installation Remote Sensing 46 Operating Manual for XPR Series Power Supply...
Страница 60: ...Operation Alarms 58 Operating Manual for XPR Series Power Supply...
Страница 79: ......