Installation
3–16
975-0263-01-01
8. Strip about 2 inches (50 mm) from the jacket of the AC input cable.
The AC input cable may be either solid or stranded, but must have
three conductors and be sized as in Table 3-3 on page 3–14. (The AC
terminal block accepts wire sizes up to No. 10 AWG.)
9. Strip approximately 3/8 inch (10 mm) off the insulation of each
conductor.
10. Run the AC cable through the right-hand side strain-relief clamp and
into the wiring compartment.
11. Fasten the Ground wire to the grounding screw.
12. Using the 1/8 inch slot screwdriver, loosen the wire attachment
screws on the terminals.
13. Insert the Line and Neutral wires into the corresponding terminals.
14. Tighten the wire attachment screws to a torque of 1.3–1.8 lbf-ft
(1.76–2.44 Nm). Leave some wiring slack inside the wiring
compartment.
15. Secure the strain-relief clamp.
16. See “Connecting AC Output to an Existing AC Circuit”.
Figure 3-5
XM Series Inverter AC Wiring Compartment
Select
Utili t y
Battery
Fault
STATUS
XM1000
Input Voltage (V)
Input Current (A)
Output Power (W)
AC
IN
AC
OUT
GND
GND
CAUTION!
Do not connect the AC OUTto any other
source of power. Damageto unit may occur.
N
L
L
N
AC knockout
AC input
ground screw
AC output
ground screw
AC knockout
CAUTION: Reverse polarity
Improper connections (connecting a line conductor to a neutral conductor, for
example) will cause the XM Series Inverter to malfunction and may permanently
damage the inverter. Damage caused by a reverse polarity connection is not
covered by your warranty.
Содержание Xantrex PRO XM 1000
Страница 2: ...Xantrex PRO Inverter Owner s Guide ...
Страница 13: ...xii ...
Страница 19: ...2 4 ...
Страница 51: ...4 8 ...
Страница 57: ...5 6 ...
Страница 60: ...Mounting Dimensions 975 0263 01 01 A 3 Mounting Dimensions Figure A 1 XM 1800 Mounting Dimensions ...
Страница 61: ...Specifications A 4 975 0263 01 01 Figure A 2 XM 1000 Mounting Dimensions ...
Страница 73: ...C 4 ...