Installation
2–20
975-0209-01-01
Relay
timing
This diagram shows the activity of each internal relay during a generator start sequence.
Wiring size
You need #16 or #18 AWG wire to make generator connections. The wire gauge depends
on the distance between the RV Series Inverter/Charger and the generator.
Circuit
protection
Figure 2-9
Relay activity during a start sequence
Table 2-3
Stop/Stop Sequence Timing
Onan
configuration
Power Tech
configuration
Generac
configuration
B+ Hold Time
2 seconds
15 seconds
2 seconds
Preheat Time
15
7
25
Preheat to Crank Delay
2
1
0
Crank Time
25
15
15
Crank Retry Time
30
15
15
Spindown Time
3
3
3
Stop Pulse Time
60
9
60
Post Stop Pulse Wait Time
0
5
0
Max Stop Tries
1
4
1
Starter Cooldown Time
60
120
30
Max Start Tries
3
3
3
Stop
Run
Start
Time
Preheat
Relay1: Glow/Stop
Relay2: Start (Cranking)
Relay3: Preheat (Glow)
Crank
Preheat/
Stop
0 to 30 ft. (9 m)
Over 30 ft. (9 m)
18 AWG
16 AWG
Important:
All circuits (except for ground connections) connecting to the Auto Gen
Control relays must be protected with fuses rated at 5 amps or less.