Installation
40
975-0126-01-01
Terminology
A description of battery charger operation requires the use of terms that you may
not be familiar with. The following terms appear throughout the guide.
Deep Cycle
A deep cycle occurs when a battery is discharged to less than 50%
of its capacity (50% depth of discharge). A deep-cycle battery is one that is
intended to be deeply discharged and charged repeatedly.
Depth of Discharge (DOD)
The amount of energy or charge removed from the
battery bank, usually expressed as a percentage. A depth of discharge of 0%
indicates a fully-charged battery, and a depth of discharge of 100% indicates a
fully-discharged battery.
Electrolyte
Typically sulfuric acid and water. It is commonly referred to as
battery acid, and it is the fluid inside a typical lead-acid battery.
Equalization
A deliberate overcharge designed to reduce sulfation and
stratification in flooded (or wet) lead-acid batteries. Not necessary and harmful on
Gel or sealed batteries.
Plates
Made of lead
and connected to the battery terminals. These are the
terminals inside each cell of the battery. The essential chemical reactions of the
battery occur at the plates, and they are the source of the current/voltage produced
by the battery.
Sulfation
As a battery discharges, its plates become covered with lead sulfate.
With regular recharging, the lead sulfate leaves the plates and recombines with the
electrolyte. If the lead sulfate remains on the plates for an extended period of time
(over two months), it hardens, and recharging does not remove it. Sulfation
reduces the effective plate area and the battery’s capacity. Equalization of flooded
(or wet) batteries helps to reduce sulfation.
Stratification
Over time, electrolyte tends to separate. The electrolyte at the top
of the battery becomes watery while it becomes more acidic at the bottom. This
effect is corrosive to the plates. Equalization of flooded (or wet) batteries helps
reduce stratification.
Temperature Compensation
Optimal battery charging voltage is dependent on
the temperature. As the ambient temperature falls, the proper voltage for each
charge stage needs to be increased. When the ambient temperature increases, the
proper voltage for each charge stage needs to be decreased. (The RS2000 battery
temperature sensor (BTS) automatically rescales charge-voltage settings to
compensate for ambient temperatures.) The hot, cold, and warm settings are used
if a battery temperature sensor is not present. The hot setting is the default.
Содержание RS2000
Страница 1: ...RS2000 Sine Wave Inverter Charger Installation Guide RS2000...
Страница 2: ......
Страница 3: ...RS2000 Sine Wave Inverter Charger Installation Guide...
Страница 8: ...iv 975 0126 01 01...
Страница 16: ...xii...
Страница 18: ...xiv...
Страница 49: ...Installation 975 0126 01 01 31 Figure 12 Connecting the BTS Cable to Battery Temp jack...
Страница 56: ...Installation 38 975 0126 01 01 Figure 15 Inverter Charger Dimensions...
Страница 75: ......